Run Enable for
FW/RV (–xFU2
models only)
The Run Enable for FW/RV input provides a way to enable or disable the [FW] and [RV] input
terminals in real time, including a Run command from an operator keypad. This is useful for
applications that require a logic type safety interlock for FWD Run or REV Run commands.
The Run Enable for FW/RV function is assigned to an intelligent input terminal using option
code 49. When assigned, the output frequency operates as a logical AND of the Run Enable for
FW/RV input
and
a [FW], [RV], or keypad Run command input. The Run Enable for RV input
is level-sensitive, as shown in the timing diagram below. The leading edges (OFF-to-ON transi-
tions) of the Run Enable for RV input and the [FW] or [RV] input can occur in any order. The
output frequency follows the logical AND of these inputs.
Opt.
Code
Symbol
Function Name
Input
State
Description
49
ROK
Run Enable for
FW/RV
ON
[FW] and [RV] inputs and operator Run
key press operate normally
OFF
[FW] and [RV] inputs and operator Run
key press are ignored; inverter output
remains OFF
Valid for inputs:
C001, C002, C003, C004,
C005
Required
settings:
(none)
Notes:
•
This function is only available on –xFU2
models.
•
When the Run Enable for FW/RV function
is
not
assigned to any intelligent input terminal,
the FWD Run and REV Run commands
operate normally (directly control the output
frequency).
•
To ensure safe inverter operation in
networked applications, you cannot change an
intelligent terminal assignment to/from
[ROK] (option code 49) via the network.
However, you can still read an [ROK] input
assignment over the network.
[F/R] terminal
[ROK] terminal
Output
frequency
t
5
3
1
4
2
FW
TH
PLC
P24
CM1
See I/O specs on page
.
Example: (Requires input configuration—
see page
. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page
ROK
Содержание L300P Series
Страница 2: ......
Страница 42: ......
Страница 134: ......
Страница 195: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 225: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 250: ......
Страница 251: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 263: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 272: ......