L300P Inverter
Oper
ati
ons
and Monitor
ing
4–57
Setting Motor Constants
Introduction
The inverter has two separate motor constant sets named
1st
, and
2nd
. The 1st motor constant
set is the default, while the SET intelligent input selects the 2nd motor constant set. The follow-
ing table lists the V/f characteristic control methods:
The following table lists the parameters associated with motor constant settings. Set each
constant according the motor type in the application. When connecting more than one motor (in
parallel) to the inverter, set the constant values that are closest to the total capacity of the
combined motors.
Adjusting Motor
Stability
Observe the motor for instability, particularly when it is rotating at constant speed. A common
symptom of instability, sometimes called “hunting,” is marked by a “rattling” sound in the
motor. To correct the instability, you can adjust some of the parameters listed above.
• Check the motor capacity (H003 / H203), and ensure it matches the capacity of your motor.
• Check the motor poles setting (H004 / H204), and ensure it matches your motor.
• If you are using a stabilization constant (H006 / H206) that is lower than the default setting,
trying raising it gradually up to the default value.
• If the motor you are using is greater than the rated capacity of the inverter, lower the value of
H006 / H206.
• If instability persists after you have checked the items above, try the procedures in the table
below. As soon as adjusting a parameter seems to produce stability, don’t change the param-
eter further. If adjusting a parameter has no effect, restore it to its original (or default) value.
V/f Characteristic Control Method
1st motor
2nd motor
V/f constant torque
✔
✔
V/f variable torque
✔
✔
V/f free-setting curve
✔
✔
Func.
Name
Data
Notes
A044 /
A244
V/f characteristic curve selection,
1st / 2nd motors
00
V/f constant torque
01
V/f variable torque
02
V/f free-setting curve
H003
Motor capacity, 1st motor
0.2 – 75
Units: kW
H203
Motor capacity, 2nd motor
0.2 – 75
Units: kW
H004
Motor poles setting, 1st motor
2 / 4 / 6 / 8
Units: poles
H204
Motor poles setting, 2nd motor
2 / 4 / 6 / 8
Units: poles
H006
Motor stabilization constant, 1st
motor
100
—
H206
Motor stabilization constant, 2nd
motor
100
—
Func.
Name
Data Range
Procedure
A045
Output gain
20 – 100
Lower this value
B083
Carrier frequency
0.5 – 8.0
Lower this value
H006 / H206
Motor stabilization constant
0 – 255
Lower or raise this value
Содержание L300P Series
Страница 2: ......
Страница 42: ......
Страница 134: ......
Страница 195: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 225: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 250: ......
Страница 251: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 263: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 272: ......