Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–46
Run Time /
Power-On Time
Over Signals
L300P Series inverters accumulate the total hours in Run Mode (run time) and the total hours of
power-ON time. You can set thresholds for these accumulating timers. Once the threshold is
exceeded, an output terminal will turn ON. One use of this is for preventative maintenance. A
signal light or audible alert could signal the need for servicing, calibration, etc.
Opt.
Code
Symbol
Function Name
Output
State
Description
11
RNT
Run Time Over
ON
when the accumulated time spent in Run
Mode exceeds the limit (B034)
OFF
when the accumulated time in Run Mode
is still less than the limit (B034)
12
ONT
Power-ON Time
Over
ON
when the accumulated power-ON time
exceeds the limit (B034)
OFF
when the accumulated power-ON time is
less than the limit (B034)
Valid for
outputs:
11, 12, AL0 – AL2
Required
settings:
B034
Notes:
•
The two outputs [RNT] and [ONT] share the
same time threshold parameter, B040.
Typically, you will use either the [RNT] or the
[ONT] output only—not both at once.
•
These outputs are useful for the notification
that a preventative maintenance interval has
expired.
See I/O specs on page
4–8
Inverter output terminal circuit
12C
12A
11C
11A
+
–
24VDC
L
Example: (Requires output configuration—
see page
RNT or
ONT
Содержание L300P Series
Страница 2: ......
Страница 42: ......
Страница 134: ......
Страница 195: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 225: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 250: ......
Страница 251: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 263: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 272: ......