4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
102
Alarm code
C1-71
Compressor Internal Thermo Activation
Alarm stop reason
Compressor motor overheats, activating internal thermo. (Activation point: 115ºC)
?
N O T E
Causes alarm stop with 3 occurrences in 30 minutes. Retry control until the second one (Compressor stops, and restarts automatically
once de thermostat returns to a normal operation temperature)
Retry indication
LCD: By touching “Inspection”, “49C Retry” is shown in “No.1 Cycle”.
Retry code
C1-P5
PCB monitoring position
PCBd (I/O PCB) PCN207 (Internal thermo for compressor (49C))
Power source too high or too low
Phase unbalance of the power source
voltage
Lock status of compressor motor
Decrease of insulation of compressor motor
Check of wiring (disconnection)
Revision of connections
Check of compressor (internal disconnection)
Check of PCBd (I/O PCB)
Yes
Yes
Remove the wiring
inserted into connector
PCN207 on PCBd (I/O PCB)
and mesure conductivity. Is
there conductivity?
No
No
No
Yes
Operation
control results
in retry status
immediately
The connection and
insertion of connector
CN207 on PCBd (I/O PCB)
are correct