4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
115
4
Alarm code
11-11
Inlet water temperature abnormality (CN4)
Alarm stop reason
Thermistor for detection of inlet water temperature (Twi) indicates an abnormal value.
PCB monitoring position
PCBc (CPU PCB) CN4 (Inlet water temperature thermistor (Twi))
?
N O T E
Refer thermistor characteristics chapter.
Replacement of thermistor
Revision of connections
Replacement of PCBc
(CPU PCB)
Yes
Yes
No
No
The connection and insertion of the connector
CN4 on PCBc (CPU PCB) is correct
Remove the connector and measure
the resistance value. Is the resistance value
normal?
Alarm code
12-12
C1-12
Outlet water temperature THM abnormality (CN5)
Alarm stop reason
Thermistor for detection of outlet water temperature (for water temperature control Two1) indicates an abnormal value.
PCB monitoring position
PCB
c
(CPU PCB) CN5 (Outlet water temperature thermistor (Two1))
?
N O T E
Refer thermistor characteristics chapter.
Replacement of thermistor
Revision of connections
Replacement of PCBc
(CPU PCB)
Yes
Yes
No
No
The connection and insertion of the connector
CN5 on PCBc (CPU PCB) is correct
Remove the connector and measure
the resistance value. Is the resistance value
normal?