4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
108
Alarm code
C1-24
Liquid THM abnormality (CN24)
Alarm stop reason
Thermistor for detection of heat exchanger outlet (Tl) (condenser liquid) temperature indicates an abnormal value.
PCB monitoring position
PCBd (I/O PCB) CN24 (Liquid thermistor (Tl))
?
N O T E
Refer thermistor characteristics chapter
Replace thermistor
Correction of connections
Replace PCBd (I/O PCB)
The connection and
insertion of connector
CN24 on PCBd (I/O PCB)
are correct
Yes
Yes
No
No
Removet he
connectors and
measure thermistor resistance.
Is resistance value
normal?
Alarm code
C1-25
Outlet rear side THM abnormality (CN25)
Alarm stop reason
Thermistor for detection of heat exchanger outlet (Two2) (rear side = internal part of the heat exchanger) indicates an
abnormal value.
PCB monitoring position
PCBd (I/O PCB) CN25 (Outlet rear side thermistor (Two2))
?
N O T E
Refer thermistor characteristics chapter
Replace thermistor
Correction of connections
Replace PCBd (I/O PCB)
The connection and
insertion of connector
CN25 on PCBd (I/O PCB)
are correct
Yes
Yes
No
No
Remove the
connectors and
measure thermistor resistance.
Is resistance value
normal?