![Hitachi 8E040341 Скачать руководство пользователя страница 76](http://html.mh-extra.com/html/hitachi/8e040341/8e040341_service-manual_21085076.webp)
3 Servicing
Cycle components
SMGB0120 rev.0 - 11/2017
68
3
Remove the 2 Victaluic connections from the
water connections.
Victaulic
connections
4
Screw eyebolts to both sides of the condenser
to the bolts for that purpose. Fasten a textile
belt to proceed to lift the condenser.
!
C A U T I O N
Do not never use chains or metallic ropes to lift the
condenser as they can damage the condenser.
5
Unscrew the 4 screw of the foot plate heat
exchanger.
4 Screws
2 foot plate
exchanger supports
6
Remove the condenser. Softly lift the
condenser and place it on a strong and stable
surface.
!
C A U T I O N
In spite of water shut-off valves are closed, water inside the plate heat exchanger and water pipe remain.
!
C A U T I O N
Plate heat exchanger is heavy, two persons and a portable crane or similar are required.