4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
106
Alarm code
14-14
C1-14
Hot Water Over-Increase
Alarm stop reason
Outlet water temperature exceeds 62ºC during compressor operation.
PCBc (CPU PCB) PCN13 short line is disconnected
?
N O T E
“
14-14
” in case that PCN13 short line is disconnected
“
C1-14
” in case of detection by outlet water temperature thermistor
PCB monitoring position
PCBc (CPU PCB) CN5 (Outlet water temperature thermistor Two1(for water temperature control))
PCBc (CPU PCB) PCN13 (Short line)
Clogging of water strainer
Adjustment of cold water thermo setting
value. Shall be within usage range
Clogging of water side heat exchanger
Adjustment of reverse rotation of pump
Adjustment of water amount (inlet-outlet
water temperature)
Replace thermistor
Correction of
connections
Check PCBc (CPU PCB)
The connection and
insertion of connector
CN5 in PCBc (CPU PCB)
are correct
Yes
Yes
Yes
No
No
No
Outlet water
temperature increased
over 62ºC during compressor
operation. (Confirmed from
data immediately before)
Remove the
connectors and
measure thermistor resistance.
Is resistance value
normal?
?
N O T E
• Hot water overincrease is detected by the outlet water temperature thermistor for water temperature control.
•
The relation between detected thermistor and alarm indication, as well as their connected PCB codes are shown in the table below.
Abnormality code
Detected thermistor
PCB code
Connector code
C1-14
Outlet water temperature thermistor Two1
PCBc
CN5