Alarms
Compressor overload (code: AL24)
Phase relay protection (Code : AL23)
There is a phase relay for three phase units.
If AL23 alarm is activated, open the control
box panel to find the phase relay
1.) “Normal” green light on means that
phase connection is correct.
2.) “PR” red light on means that phase
connection is reversal.
3.) “PL” red light on means that there is a
loss of one or more phases.
If AL24 alarm is activated, open the control
box panel to find the thermal overload
relay and press 'RESET".
24)
he control
load
4.) “O UVR-VOLT” red light on means that power supply
voltage is too high/low.
After correcting the phase problem, then press to reset
the alarm.
After re-setting thermal overload relay, then press <
> to reset the alarm.