26
User Guide
Changing Set points (for user)
Display
Procedures
press <Prg> to main menu, press Down button to User, Press Enter button,
Press Down button to the desired parameter.
Press Enter button, when 7.0 is flashing, press Up or Down button to
change the value.
Press Enter to confirm.
Cursor will move to next parameter data 40,
40 will flash and could be changed via up or down button.
Press Enter to confirm,
Cursor will move to setpoint,
When setpoint is flashing, press Down button to next parameters.
Or, continuously press <Esc> to exit out of the current level and back to the desired menu level.
User
S02
Setpoint
ST01: Cooling
ST02: Heating
7.0
℃
40.0
℃
User Parameters
User parameters could be adjusted when the unit is ON or OFF.
Para-
meter
Descriptions
De-
fault
Min.
Max.
Unit
Res
System mode Cooling or heating
ST01
Setting temperature at cooling mode
7
ST11
ST12
ºC
0.1
ST02
Setting temperature at heating mode
40
ST13
ST14
ºC
0.1
ST03
Setting temperature difference at cooling mode
2
0
10
ºC
0.1
ST04
Setting temperature difference at Heating mode
2
0
10
ºC
0.1
ST05
Setting temperature at heating compensation
25
0
30
ºC
0.1
ST06
Compensation factor for heating compensation
0.6
0
30
-
0.1
ST07
Outdoor temp. to start the boiler or electric heater
0
-20
20
ºC
0.1
ST09
Hot water temperature
50
ST15
ST16
ºC
0.1
ST10
Hot water temperature difference
3
1
10
ºC
0.1
ST26
Disinfect time
0
0
1000
h
1
ST27
Disinfect temperature
65
50
99.9
ºC
0.1
TR09
AC timezone On/Off
NO
YES or NO
TR10
HW timezone On/Off
NO
YES or NO
SF04
Enable weather compensation
NO
YES or NO
Содержание AS10/LF
Страница 8: ...6 Positioning Outdoor unit 1600mm 600mm 550mm 600mm Indoor unit 800 50 800 800...
Страница 51: ...48 Dimensions AS10 LF AS13 LF Indoor unit Outdoor unit 633 600 955 600 1023 999 1028 999 1050 650 400 420...
Страница 53: ...50 Water Pressure Plots UPM3 FLEX AS 25 70 130 Optional water pump 2 curve AS10 LF...