Three curves of different ST05 setting:
If SF04: Enable compensation =Yes,
S10 menu is popped up :
S10
ST05=25.0
℃
0T:
Actual setp:
ST06=0.6
-09.3
℃
45.5
℃
Press
to change ST05 and ST06, OT is actual
read ambient temp. Actual control temp. ST will be
displayed.
Press
to menu S11:
S11
ST05=25.0
℃
0T:
Heat setp.=
ST06=0.6
00.0
℃
40.0
℃
You could input any OT value ,press
and relative
heating control temp. will be calculated.
If OT=-15.0
℃
, actual control temp. is 49.0
℃ .
S11
0T:
Heat setp. =
-15.0
℃
49.0
℃
If you have your own curve as below, you want to have
ST =38
℃
when OT=0
℃
and ST=49
℃
when OT=-10
℃
Just adjust wanted T1,T2,OT1 and OT2 in S12 menu
and it could help to find out relative ST05 and ST06
setting for desired control outlet water temp in certain
OT.
S12
T1: 38
℃
T2: 49
℃
ST05=18.1
0T1: 00.0
℃
0T2: -10.0
℃
ST06=1.1
As above example, ST05=18.1 ST06=1.1 ,then go
to menu S10 to input checked result into ST05 and
ST06 parameter and you will get the desired weather
compensation setting .