Systems Overview
Heating Mode Working Principle:
On heating mode
a. When SF04:enable compensation=NO,
When the Inlet water temperature≤ RTc-ST04 (RTc
is the actual read Inlet water temperature of the
last stop) , the compressor will start to heat. After
outlet water temp. B2≥ST02, compressor will stop.
The Compressor will start again when Inlet water
temperature≤RTc-ST04,.
b. When SF04 enable compensation=YES,
ST02 is replaced by “Set temperature at heating”
=ST05+ST06/10 *(ST05-OT). Refer to chapter
“Heating compensation curve setting” .
Cooling Mode Working Principle:
When the Inlet water temperature B1
≥
RTc+ST03
(RTc is the actual read inlet water temp. of last stop),
the compressor will start to cool until Outlet water
temperature B2
≤
ST01. Then compressor will stop.
The Compressor will start again when Inlet water
temperature B1
≥
RTc+ST3.