![Hioki PW3336-01 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/hioki/pw3336-01/pw3336-01_instruction-manual_2137351036.webp)
2.2 Connecting the Measurement Lines
30
Connecting the measurement lines
Please read "Handling the Instrument" (p.6) carefully before connecting the instru-
ment to the measurement lines.
Connect cables to the instrument’s voltage and current input terminals.
You will need: A Phillips head screwdriver with a No. 3 tip
• Verify that power to the measurement lines has been cut off before connecting the
instrument to them.
• To avoid electric shock or a short-circuit at the input terminals, use solderless termi-
nals that cover wiring with insulation.
• To prevent instrument damage or electric shock, use only the screws (M6
×
12 mm)
for securing the voltage input terminals and current input terminals in place and the
screws (M3
×
6 mm) for securing the safety cover in place that shipped with the prod-
uct. If you loose any screw or find that any screws are damaged, please contact your
Hioki distributor for a replacement.
Safety covers
• The safety covers play a protective role by preventing contact with the terminals. Always attach the covers
before using the instrument.
• Verify that no voltage is being applied to the measurement lines before attaching or removing the safety
covers.
1
Remove the safety covers from the voltage input terminals and current input terminals.
2
Connect the cables to the voltage input terminals and current input terminals.
3
Attach the safety covers.
Remove the safety cover.
2
Remove the screws. (M3 × 6 mm)
1
Input terminal tight-
ening torque: 3 N
•
m
1
Remove the screws with the Phillips head screwdriver.
2
Position each wire as shown in the figure and secure in
place with the screw. (M6 × 12 mm)
Screw
(M6 × 12 mm)
Wire
• Use solderless terminals with a width of 13 mm or less.
• Tighten screws securely.
e.g.) Voltage input terminal
e.g.) Current input terminal
Solderless terminal
(Width 13 mm or less and
capable of accommodat-
ing an M6 screw)
Attach each cover securely.
Содержание PW3336-01
Страница 2: ......
Страница 6: ...Contents iv...
Страница 16: ...Operating Precautions 10...
Страница 32: ...1 4 Measurement Workflow 26...
Страница 44: ...2 7 Turning Off the Instrument 38...
Страница 180: ...5 6 Wiring Specifications 174 3 3 phase 3 wire 3P3W 3P3W2M 4 3 phase 3 wire 3V3A 3P3W3M Current sensor...
Страница 181: ...5 6 Wiring Specifications 175 5 3 phase 4 wire 3P4W Current sensor...
Страница 182: ...5 6 Wiring Specifications 176...
Страница 199: ...Appendix 4 Dimensional Diagram A13 e g PW3337 03 Appendix 4 Dimensional Diagram Unit mm...
Страница 200: ...Appendix 4 Dimensional Diagram A14...
Страница 203: ......
Страница 204: ......
Страница 205: ......
Страница 206: ......