5.1 Basic Specifications
44
Power Factor
Frequency measurement
Operation Method for Totalization
Other Characteristics
Measurement
Range
Power factor PF 0 to 1
Measurement
Accuracy
±5%rdg.
(At full-scale input with power factor of 1)
Measurement
Range
Frequency FREQ 40Hz to 70Hz
Measurement
Accuracy
±0.5%rdg.
(When input is 70% to 130% f.s. of voltage
range)
Object to be
Measured
Voltage U1
Start of
Totalization
The PC application starts measurement.
End of Totaliztion
The PC application ends measurement
(depending on recording end conditions).
For details, refer to specifications of the PC
application.
Temperature
Within ±0.05 f.s./°C
Effect of
Maximum Rated
Voltage to Earth
Within±0.5%f.s.
(Maximum rated voltage to earth 50Hz/60Hz)
Actual Time
Accuracy
±100 ppm
(Reference value at temperature from 0 to
50°C (32 to 122°F) without using
communications module)
Effect of
Electromagnetic
Field
Within ±2% f.s.
(in field of 400 Vrms/m and 50/60Hz)