Commissioning
89/146
9.3
Testing
Process data
Ø
Select the desired wireless port (WP01, WP02, WP03, ...) in the left
column of the netFIELD Wireless Web Server.
Ø
Open the
Process Data
tab.
Ê
The following process data are the result of the represented
commissioning example with a laser distance sensor.
Figure 45: Tab and table “Port process data” (example PD input valid = OK)
Note:
Displayed values coming from a real sensor, can change if sensor
conditions change.
Status
Ø
Select the desired wireless port (WP01, WP02, WP03, ...) in the left
column of the netFIELD Wireless Web Server.
Ø
Open the
Status
tab.
Ê
The following port status data are the values displayed after
configuration steps for the IO-Link Wireless Master and the port
configuration are completed.
Figure 46: Status tab, Port status
The displayed values are real values from the device.
Parameter
Displayed values
Parameter
Displayed values
Port state
Operate
Output data length 0 Bytes
Port quality
PDI invalid, PDO invalid
Vendor ID
0x136
Revision ID
0x11
Device ID
0x174
Master cycle time
15 ms
Signal quality
15 %
Input data length
2 Bytes
Table 50: Status tab, Port status, displayed values
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public