Configuration
77/146
Required rights
Changes to settings require operator or admin rights. If these are not
available, the ISDU tab is grayed out and the displayed values cannot be
edited.
Access to IO-Link Wireless Master device
To access the data of the IO-Link Wireless Master via PortId and
ArgBlockId (ISDU message format):
Ø
In the menu on the left, select the wireless IO-Link port of the IO-Link
Wireless Master to which an IO-Link Device is connected.
Ø
Open the
ISDU
tab.
Ê
The ISDU tab is displayed.
Ø
Enable
Tigo Master Parameters
.
Ê
The Tigo Master Parameters tab variant is displayed.
Read access to IO-Link Wireless Master device
To read data from the IO-Link Wireless Master device, proceed as follows:
Ø
Enter the
PortId
of the IO-Link Wireless Master device that you want
to access as a hexadecimal value in the
PortId
entry field.
Ø
Enter the
ArgBlockId
of the IO-Link Wireless Master that you want to
access as a hexadecimal value in the
ArgBlockId
entry field. The
default value here is
00
.
Ê
In case of input errors, an error message appears.
Ø
Click on
Read
.
Ê
The read access is executed. An entry with a time stamp is written to
the history at the bottom of the ISDU tab.
If the execution was successful, the text
Read ok:
and the result is
displayed in the history. The entries in the history then have the following
structure:
Time - PortId:ArgBlockId - Read ok: <Result>
If the execution was not successful, an error message with error codes of
the IO-Link Wireless Master and IO-Link Device is displayed in the history.
In this case, the entries in the history have the following structure:
Time - PortId:ArgBlockId - Read failed:
IOLMErrorCode(<error code of the IO-Link master>):
IOLDErrorCode(<error code of the IO-Link Device>)
Information on the meaning of the error codes of the IO-Link master
(IOLMErrorCode) and device (IOLDErrorCode) can be found in the
IO-Link specification.
The following applies in both cases:
·
The
Time
is displayed in the format
HH:MM:SS
·
PortId
and
ArgBlockId
are displayed in hexadecimal format.
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public
© Hilscher 2020 - 2022