Configuration
32/146
Parameter group
Parameter
Default Value range
Description
Wireless IO-Link port
parameter
(for WP01/WP02/ …)
Enable port diagnosis
1
0: Disable
The PROFINET port diagnosis is
deactivated, i.e. no diagnostic
alarms are triggered.
1: Enable
The PROFINET port diagnosis is
activated.
Enable process alarm
(device notification)
1
0: Disable
PROFINET process alarms are
deactivated.
1: Enable
PROFINET process alarms are
activated.
Configuration source
1
0:
The configuration is done via a "Port
and Device Configuration Tool".
1:
The configuration is done via the
PROFINET IO-Controller.
Enable input fraction
0
0: Disable
Input fraction is deactivated.
1: Enable
Input fraction is activated.
Enable pull/plug
1
0: Disable
PROFINET Pull/Plug alarms are
deactivated.
1: Enable
PROFINET Pull/Plug alarms are
activated.
Port mode (operating
mode of IO-Link port)
2
0: Deactivated
The W-port is inactive. Input and
output process data is 0.
1: IO-Link Wireless
cyclic
The W-port operates in cyclic mode.
2: IO-Link Wireless
roaming
The W-port operates in roaming
mode.
Validation / Backup
No
Device
check
No Device check
There is no device check for
validation or backup of connected
IO-Link Devices (default).
Type compare,
no Backup/Restore
A device check is performed for
validation of connected IO-Link
Devices to the specified device type,
without backup/restore.
Type compare,
Restore only
A device check is performed for
validation or restore of connected
IO-Link Devices to the specified
device type, without backup.
Type compare,
Backup and Restore
A device check is performed for
validation or backup/restore of
connected IO-Link Devices to the
specified device type.
Port cycle time
0
0 … 255
cycle time of the IO-Link Wireless
Master
Vendor ID
0
0 … 65535
See ioddfinder.io-link.com, or the
documentation of the manufacturer
of the W-Device (IO-Link Device
connected via a wireless connection
to the IO-Link Wireless Master)
used.
Device ID
167772
15
0 … 16777215
Wireless slot number
0
0 … 7
Wireless slot number to be used for
the port
Wireless track number
0
0 … 2
Wireless track number to be used
for the port
Wireless device TX
power
31
1 … 31
This parameter contains the
transmit power level of the W-
Device