Configuration
33/146
Parameter group
Parameter
Default Value range
Description
Wireless IO-Link port
parameter
(for WP01/WP02/ …)
Wireless max retry
8
2 … 31
Maximum number of retries for a
transmission in OPERATE mode
Wireless IMA time
3 s
1.664 ms … 10 min
Requested I-Am-Alive time for the
OPERATE mode
See table
Wireless slot type
0
0: Single slot
Slot type is “single slot”
1: Double slot
Slot type is “double slot”
Wireless low power
device
0
0: Disable
The connected W-Device is not a
low power device.
1: Enable
The connected W-Device is a low
power device.
Wireless max PD
segment length
2
1 ... 32
This parameter contains the
maximum segment length of the
PDOut data to the Message handler
to distribute PDOut Data within
multiple W-Cycles.
Wireless Unique ID of
the W-Device Byte 0
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 1
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 2
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 3
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 4
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 5
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 6
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 7
0
0 … 255
UniqueID of the W-Device
Wireless Unique ID of
the W-Device Byte 8
0
0 … 255
UniqueID of the W-Device
Table 16: Parameters of the submodules IO-Link Wireless Device XX I / XX O + PQI
(Expert)
Port cycle time
The parameter “Port cycle time” sets up the cycle time of a W-Port of the
W-Master. The cycle time is encoded using "Time base" (bits 6+7) and
"Multiplier" (bits 0-5) values, as shown in the following table:
Range of
values
Time base
(Bits 7+6)
Multiplier
(Bits 5-0)
Resulting Cycle time
0
00
0
free-running mode
Note: If the free-running mode is chosen with a time base of 0, the W-
Master stack will automatically configure the Master cycle time to be the
Minimum Master cycle time based on the PD Segmentation length, Slot
Type, and Max Retry configurations.
1 … 64
00
1 … 63
65 … 127
01: 5ms
1 … 63 as
multiplier
5 ... 315 ms (Time Base * Multiplier)
Note: For W-Devices and W-Bridges the minimum possible transmission
time is 5 ms.
128 … 255
10 ...11:
reserved
1 … 63
reserved, do not use
Table 17: Calculation of the port cycle time of the IO-Link Wireless Master
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public
© Hilscher 2020 - 2022