Configuration
47/146
8.3.6.4
Factory settings
In some cases, it is helpful to reset the device to the factory settings. This is
possible for various selectable classes of settings via the Factory reset tab
in the Settings menu.
Figure 13: Factory reset tab
Changes to settings require operator or admin rights. If these are not
available, the tab is grayed out and cannot be edited.
Important:
If PLC communication is active, factory reset is not allowed! Stop
PLC communication before you use the factory reset options.
Various settings made can be deleted depending on your selection:
Option
Delete stored configuration
Delete stored
device
information
Device information (e. g. maintenance information, system time settings,
and IO-Link master settings within OPC UA)
Delete stored
network adapter
settings
Network adapter settings (communication settings, IP address
configuration, Name of Station)
Delete stored
application
parameters
Application-specific data (port configuration and parameters, remanent
parameters)
Delete all stored
settings
All settings
Table 23: Options to delete settings
To reset the device to the factory settings, proceed as follows:
Ø
Click on the
Settings
in the left column of the netFIELD Wireless Web
Server.
Ê
The Device configuration tab appears.
Ø
Select the
Factory reset
tab.
Ø
Select which settings should be reset to the factory defaults.
Ø
Click on
Delete settings
.
ð
The selected settings are deleted.
ð
Click on
Restart
.
ð
The device is restarted with the factory settings.
NFD-3090-PNS-IOLM\W | Hardware, installation and commissioning
DOC201101UM03EN | Revision 3 | English | 2022-02 | Released | Public