26/46 Operation
Hengst Filtration GmbH
Hengst Filtration GmbH
, RE 51550-B/04.2021
, RE 51550-B/04.2021
5.1.7.6 Switching output x: Testing the switching output
A test of the switching output can be started in the following menu:
The following options are available:
Test possibility for the switching output
Options for setting
OUi
to
hNO
/
hNC
/
fNO
/
fNC
:
Normal operation of
the switching output
Permanently switch off
the switching output
Permanently switch on
the switching output
Options for setting
OUi
to
fM
:
Normal operation as
frequency output
Output
Frequency 1 Hz
Output
Frequency 100 Hz
Important notice
:
When the test is complete, set the function to
normal operation
N.Op
.
5.1.7.7 Change display function of the status LED
The switching status of the output is indicated by the LEDs in the display.
The assignment of the LEDs to the switching output is shown in the following table:
Numbering
LED
Switching output x
Assignment with
2 switching outputs
1
Reserved for IO-Link
2
LED 2 - red
3
Reserved
4
Reserved
5
Reserved
6
Reserved
In the factory setting, the LED indicates the physical state of the PNP switching
output (switching output closed - LED illuminated).
It is possible that the logic function of the display shall be different from the physical
signal on the switching output. You can therefore also reverse this display in this
menu item (switching output open - LED illuminated).