38/46 Appendix
Hengst Filtration GmbH
Hengst Filtration GmbH
, RE 51550-B/04.2021
, RE 51550-B/04.2021
9.3 Technical data WGM-R / WGM-D
Remote display / sensor with display
Evaluation and indication electronics
Display
4-digit, 7-segment LED
Indicator unit
0 - 100% relative humidity
Operation
using 3 keys
Memory
Storage of min./max. values
Current consumption
upon switch-on
approx. 100 mA for 100 ms
Current consumption in
operation
approx. 50 mA (no current nor switching outputs)
Supply voltage (U
B
)
18 - 30 V DC (nominal voltage 24 V DC)
Ambient temperature
-20 °C to +70 °C
Display resolution
0.5%, 0.5 °C, °F
Version
WGM-R
Remote display for sensor
Dimensions
Fastening
35 mm profile rail mounting
90,39
40
53
105
Weight
approx. 130 g without
sensor
Display housing
PA
Protection class
IP65* (display)
* with fitted plug-in
connector
Version
WGM-D
with built-on sensor
Dimensions
Fastening
G 3/4
141
Ø
16
G 3/4
40
15
16
36
53
Weight
approx. 270 kg
Display housing
PA
Protection class
IP65* (display)
* with fitted plug-in
connector
IO-Link
IO-Link
Revision 1.1
Baud rate
COM3 (230.4 k)
SIO mode
Yes
Min. cycle time
10 ms
Humidity measurement
Measurement range
0 - 100% rel. humidity
Accuracy
± 3 % FS