28/46 Operation
Hengst Filtration GmbH
Hengst Filtration GmbH
, RE 51550-B/04.2021
, RE 51550-B/04.2021
Temperature
Assignment of the temperature level where the maximum analog signal will be
output. The setting is made in the menu:
The following options are available:
Setting range: -20 °C to 120 °C [-4 °F to 248 °F]
Notice:
▶
The set output range must not be smaller than 10% of the
measurement range:
ai.hI
-
ai.lO
> = 10%
▶
If the selected range is too small, the analog value output may have
increments.
5.1.8.3 Analog output x: Assignment of the lower limit
Humidity
Assignment of the humidity level where the minimum analog signal will be output.
The setting is made in the menu:
The following options are available:
Setting range: 0% to 100%
Notice:
▶
The set output range must not be smaller than 10% of the
measurement range:
ai.hI
-
ai.lO
> = 10% * (
0
-
100
)
▶
If the selected range is too small, the analog value output may have
increments.
Temperature
Assignment of the temperature level where the minimum analog signal will be output
here. The setting is made in the menu:
The following options are available:
Setting range: -20 °C to 120 °C [-4 °F to 248 °F]
Notice:
▶
The set output range must not be smaller than 10% of the
measurement range:
ai.hI
-
ai.lO
> = 10%
▶
If the selected range is too small, the analog value output may have
increments.