33
OPERATING PRESSURES
Minimum/Maximum ..................................................................................................................................25 psi-125 psi
OPERATING TEMPERATURES
Minimum/Maximum ..................................................................................................................................40º - 110º F
1-1/2” METER
Accuracy ...................................................................................................................................................±5%
Flow Rate Range......................................................................................................................................0.5 - 60 GPM
Gallon Range ...........................................................................................................................................500 - 250,000
DIMENSIONS
Drain Line .................................................................................................................................................3/4” or 1” NPT
Brine Line .................................................................................................................................................1/2” Poly Tube
ELECTRICAL CURRENT DRAW AND VOLTAGE
..................................................................................................0.5A 110v
Compatible with the following regenerants or chemicals: Sodium chloride, potassium permanganate, sodium bisulfite, sodium hydroxide,
hydroxide, hydrochloric acid, chlorine and chloramines.
GENERAL SPECIFICATIONS
PROGRAMMING OPTIONS
AUTO
Delay
oFF
Reserve capacity automatically estimated.
Regeneration occurs when gallons capacity falls below the reserve capacity at the next
Regen Set Time.
AUTO
Delay
1 to 28
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity falls below the
reserve capacity or the specified number of days between regenerations is reached.
Delay
oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity reaches 0.
Delay
oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the specified number of days
between regenerations is reached.
Delay
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity reaches 0 or the
specified number of days between regenerations is reached.
AUTO
Immediate
oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when gallons capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration will always
occur when gallons capacity reaches 0.
Immediate
oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when gallons capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration will always
occur on 0.
AUTO
Delay + Immediate
oFF
Reserve capacity automatically estimated.
Regeneration occurs when gallons capacity falls below the reserve
capacity at the next Regen Set Time or regeneration occurs immediately after
10 minutes of no water usage when gallon capacity reaches 0.
AUTO*
Delay + Immediate
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity
falls below the reserve capacity or the specified number of days between regenerations
is reached or regeneration occurs immediately after 10
minutes of no water usage when gallon capacity reaches 0.
Delay + Immediate
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when specified number of days
between regenerations is reached or regeneration occurs immediately after 10 minutes
of no water usage when gallon capacity reaches 0.
1 to 28
1 to 28
1 to 28
1 to 28
*14
20 to
250,000
20 to
250,000
20 to
250,000
20 to
250,000
Reserve
Gallons
Regeneration
Type
Days
Override
Results
(Reserve capacity estimate based on history of water usage)
*Factory settings in bold
To "lockout" access to modification settings, diagnostic and valve history displays except hardness, day override and time,
press
X
next,
X
and clock in sequence to "unlock" press
X
next,
Z
and clock in sequence.