Step 5CS – Set Auxiliary Drive Output (MAV only) to operate in one of three modes:
• Set RECLAIM (Time): Allows Auxiliary MAV to switch positions at a set time in relation to the start
of regeneration for a preset duration, independently of the actual regeneration status. Up to 3 bypass
events are possible.
• Set SEP SOURCE: Allows Auxiliary MAV to switch positions before the start of regeneration and
then switch back at the end of regeneration.
• Set OFF: Deactivates this output.
Only use Clack Motorized Alternating Valves (MAV) with these selections. Clack No Hard Water Bypass
Valves (1” or 1.25” V3070FF or V3070FM) are not designed to be used with the reclaim or separate source
functions.
Press NEXT to go to Step 6CS. Press REGEN to return to previous step.
STEP 11CS –
Only displays if reclamation of brine is enabled in Step 10CS. Use the
or
buttons to select the number of minutes after the start of regeneration before the MAV will divert
the brine waste water from the plumbing drain receptacle to the brine tank. Start of regenera-
tion is defined as any mode that is not fill or softening.
Press NEXT to go to Step 12CS. Press REGEN to return to previous step.
STEP 12CS –
Only displays if reclamation of brine is enabled in Step 10CS. Use the
or
buttons to select the number of minutes to divert the brine waste water to the brine tank. After
the minutes count down to zero the waste water will once again be diverted to the plumbing
drain receptacle.
Press NEXT to go to Step 13CS. Press REGEN to return to previous step.
AUX RECLAIM DURATION
AUX RECLAIM DURATION
AUX RECLAIM DURATION
X
Brine Reclaim:
When Reclaim is selected as trigger for Auxilliary MAV Drive, a portion of the brine can be diverted after it has passed through
the resin bed. Brine discharge contains unused salt that can be used for brine make-up for the next regeneration. A motorized alternator valve
(MAV) must be connected to the two-pin connector labeled AUX 1 located on the circuit board or error code 106 will result. The MAV diverts the
brine discharge to brine tank. A-Port discharges to brine tank. B-Port discharges to drain, remaining port connects to the valve drain fitting. For
start time and duration settings an elution study must be done to provide settings that optimize salt savings without sacrificing capacity.
H151 Super HP Software REV (P101, P100.11 & >) defines start of regeneration as any mode that is not fill or softening.
H151 HP Software REV (P200.25 & >) defines start of regeneration as the start of brine draw and backwash time must be subtracted
from start time. See REV sticker on top of PC board to identify software, see page 38-39 for backwash times.
AUX MAV SEP SOURCE
SET
STEP 13CS
TRIGGER
STEP 13CS –
Separate source selection requires connection of motorized alternator valve (MAV) to
Auxiliary Drive two-pin connection on board.
Auxiliary MAV Drive set to operate with a Separate Source trigger. Auxiliary MAV transitions to Bypass
before the start of regen cycle #1, AFTER Alternator MAV motor transition. Auxiliary MAV transitions
back to Service at the completion of the last programmed regen cycle, once the Valve Motor deactivates
and BEFORE Alternator MAV transition (if scheduled). Auxiliary MAV will NOT automatically return to
Service while manually stepping valve through regen, MAV will remain in Bypass until regen cycle ends
or NEXT & REGEN buttons pushed simultaneously until display changes. Press NEXT to go to Step
14CS. Press REGEN to return to previous step.
STEP 14CS –
This display will be available to select the use of an outside signal to control the initia-
tion of a regeneration. Selection only matters if a connection is made to the two pin connector labeled DP
SWITCH located on the printed circuit board. Following is an explanation of the options:
• IMMED REGEN – If the dP switch is closed for an accumulative time of 2 minutes, a regeneration will
occur immediately.
• DELAY REGEN – If the dP switch is closed for an accumulative time of 2 minutes, a regeneration will
occur at the schedule regeneration time.
• HOLD REGEN – If the dP switch is closed a regeneration will be prevented from occurring.
• OFF - Factory setting is off
Press NEXT to go to Step 15CS. Press REGEN to return to previous step.
OFF
AUXILIARY INPUT
SET
REG
STEP 14CS
➔
➔
➔
➔