Installation and Operating Instructions

–  It is recommended to maintain a system maintenance book and enter the tests and test results carried out.
  Compare the results with the results of previous audits. If the parameters vary, you should always contact the
 manufacturer.

 

–  The instructions in the maintenance manual of the electric motor must be observed.

4.1 Cleaning

  The unit must be fully isolated from the mains power supply before any cleaning work!   

  Wet cleaning under tension can lead to electric shock.

–   Regular inspection, and with periodic cleaning is required in order to avoid imbalance due to pollution. Clean the
  flow area of the fan.
–   Do not use aggressive, paint solvent agents!
–   High-pressure cleaners or water jets are not permitted!

4.2  Information – Fault causes

 

WARNING 

m

Error/Fault

Causes

Solution

Fan does not start

No voltage, phase missing

Check voltage

Impeller blocked

Clear blockage, clean, have impeller repla-
ced by manufacturer if necessary

Motor blocked

Check motor,  have replaced by manufactu-
rer if necessary

Fuse tripped

Short-circuited coil/ground fault in motor Have motor replaced by manufacturer
Supply line/connection damaged

Replace parts, have motor replaced by ma-

nufacturer if necessary

Connected incorrectly

Check connection, change

Residual current device 
tripped

Motor insulation damaged

Have motor replaced by manufacturer

Supply line insulation damaged

Replace supply lines

Motor protection  
switch triggered

Tight bearing

Have bearing replaced by manufacturer

Impeller touching

Clean, have impeller replaced by manufactu-

rer if necessary

Incorrect operating point

Check suitability of fan, Check/keep inflow 

and outflow clear

Contaminated motor

Clean

Vibrations

Contamination

Clean

Bearing damage

Have bearing replaced by manufacturer

Incorrect operating point

Check suitability of fan, Check/keep inflow 
and outflow clear

Attachment-related resonance

Check or repair attachment

Incorrect direction of rotation

Check/modify connection

Impeller imbalanced

Rebalancing by manufacturer

     EN    

Abnormal noises

Incorrect operating point

Check suitability of fan, Check/keep inflow 

and outflow clear

Grinding impeller

Clean, have impeller replaced by manufactu-

rer if necessary

Bearing damage

Have bearing replaced by manufacturer

Mechanical damage

Carry out maintenance

Incorrect direction of rotation

Check, modify connection

Power consumption too 
high

Incorrect operating point

Check suitability of fan, Check/keep inflow 

and outflow clear

Grinding impeller

Clean, have impeller replaced by manufactu-

rer if necessary

Bearing damage

Have bearing replaced by manufacturer

Fan does not perform
(speed)

Incorrect operating point

Check suitability of fan, Check/keep inflow 

and outflow clear

Incorrect voltage

Check/modify connection

Bearing damage

Have bearing replaced by manufacturer

Contamination

Clean

Insufficient backflow

Widen backflow openings

Incorrect direction of rotation

Check/modify connection

Содержание RDD 200/4 EX

Страница 1: ...Explosionsgesch tzte Baureihen Explosion proof series RD VD Dachventilatoren Roof fans DE Helios Ventilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS EN...

Страница 2: ...ND WARTUNG Seite 5 4 0 Instandhaltung und Wartung Seite 5 4 1 Reinigung Seite 6 4 2 Hinweise St rungsursachen Seite 6 4 3 Ersatzteile Seite 7 4 4 Stilllegen und Entsorgen Seite 7 KAPITEL 5 TECHNISCHE...

Страница 3: ...s durch trockene luft und staubdichte Verpackung Kunst stoff beutel mit Trockenmittel und Feuchtigkeits in di ka to ren Der Lager ort muss ersch tterungsfrei wassergesch tzt und frei von Temperatur sc...

Страница 4: ...chen Geh use und Laufrad erforderlich 1 10 Ger uschangaben Die Ger uschangaben beziehen sich auf die unter Kapitel 3 1 beschriebene Anordnung Geh usevariationen un g nstige Betriebsbedingungen etc k n...

Страница 5: ...uverh ltnisse kann ein Ber hrungsschutz saugseitig erforderlich sein Ventilatoren die durch ihre Einbauweise z B Anschluss an L ftungskan le gesch tzt sind ben tigen kein Schutzgitter wenn die Anlage...

Страница 6: ...stabstand von 1 m zum Ventilator einzuhalten Der Ventilator muss f r Reinigungs und Wartungszwecke leicht zug nglich sein insbesondere der Klemmenkasten Revisionsschalter Das Geh use darf bei der Mont...

Страница 7: ...h tung Drehrichtung des Laufrades pr fen durch kurzzeitiges Einschalten beim Pr fen der Drehrichtung eine Schutzbrille tragen Stromaufnahme mit Leistungsschildangabe vergleichen Motorschutzeinrichtung...

Страница 8: ...ntilators pr fen Zu und Abstr mung pr fen freihalten falsche Spannung Anschluss pr fen ndern Lagersch den Lager durch Hersteller ersetzen lassen Verschmutzung reinigen unzureichende Nachstr mung Nachs...

Страница 9: ...X D B C LK Y Baureihe VD 180 710 Vertikal ausblasend A B LK Y C D E H G elektrischer Anschluss X VD 180 320 245 213 6 x M6 10 309 30 175 56 Klemmen kasten VD 200 425 330 259 405 249 50 VD 225 50 VD 2...

Страница 10: ...lasse Z ndschutzart des Motors Kennzeichnung Herstelljahr Art Nr SNR Seriennummer und PC Produktionscode Nummer identifizieren den Ventilator eindeutig 5 2 Motortypenschild Eine Kopie des Motortypensc...

Страница 11: ...Farbcode nach IEC 757 U BN br braun brown V GY gr grau grey W BK sw schwarz black TP WH ws wei white PE YE GN ge gn gelb gr n yellow green TP TP 1 2 L3 L2 L1 L1 L2 L3 TP PE TP L1 L2 TP TP 3 Motor mit...

Страница 12: ...hluss Verlegung nach VDE JA 3 Mindestluftspalt gepr ft JA Wert 4 Freier Lauf des Laufrades gepr ft JA 5 Stromaufnahme gemessen vgl mit Typenschild JA Wert 6 F rder und Drehrichtung gepr ft JA 7 Schwin...

Страница 13: ...7 Fehlerschleifen Impedanz TN System oder Erdungswiderstand IT System ausreichend 8 Isolationswiderstand ist ausreichend 9 Die automatische elektrische Schutzeinrichtung spricht in zul ssigen Grenzwer...

Страница 14: ...12 RD und VD Dachventilatoren Montage und Betriebsvorschrift DE...

Страница 15: ...13 RD und VD Dachventilatoren Montage und Betriebsvorschrift Notizen DE...

Страница 16: ...eration Page 5 CHAPTER 4 INSPECTION AND MAINTENANCE Page 5 4 0 Inspection and maintenance Page 5 4 1 Cleaning Page 6 4 2 Information Fault causes Page 6 4 3 Spare parts Page 7 4 4 Put out of service a...

Страница 17: ...oisture indicators The storage place must be water proof vibration free and free of temperature variations The storage temperature of 20 C to 40 C must not be exceeded When storing for several months...

Страница 18: ...inquiry is necessary Helios explosion proof fans are in accordance with the specification ATEX Directive 2014 34 EU Equipment Safety Act For the evaluation of the explosive area an allocation into zo...

Страница 19: ...ull your fingers arms in Only operate with mounted safety devices Do not put objects into the rotating impeller Risk of damage The roof fans have a fixed direction of motor rotation which is marked on...

Страница 20: ...observed The fan must be easily accessible for cle aning and maintenance purposes particularly the terminal box isolator switch The casing must not be deformed or warped during installation minimum ai...

Страница 21: ...ller by switching on for a short time when checking the direction of rotation wear protective goggles compare current consumption with data on the rating plate test functioning of motor protection dev...

Страница 22: ...Supply line insulation damaged Replace supply lines Motor protection switch triggered Tight bearing Have bearing replaced by manufacturer Impeller touching Clean have impeller replaced by manufactu r...

Страница 23: ...0 710 Vertikal ausblasend A B LK Y C D E H G elektrischer Anschluss X VD 180 320 245 213 6 x M6 10 309 30 175 56 Klemmen kasten VD 200 425 330 259 405 249 50 VD 225 50 VD 250 580 450 286 450 279 VD 31...

Страница 24: ...f protection of the motor Classification Year of manufacture Art Nr Ref no SNR serial number and PC production code number identify clearly the fan 5 2 Motor type plate A copy of the motor type plate...

Страница 25: ...ode nach IEC 757 U BN br braun brown V GY gr grau grey W BK sw schwarz black TP WH ws wei white PE YE GN ge gn gelb gr n yellow green TP TP 1 2 L3 L2 L1 L1 L2 L3 TP PE TP L1 L2 TP TP 3 Motor mit TP KL...

Страница 26: ...on to VDE YES 3 Minimum air gap checked YES Value 4 Unhindered running of impeller checked YES 5 Current consumption measured YES Value compare with type plate 6 Airflow direction and direction of rot...

Страница 27: ...isfactory physical check visual check 7 Fault loop impedanz TN system or earthing resistance IT system satisfactory 8 Isolation resistance is satisfactory 9 Automatic electrical protective devices ope...

Страница 28: ...12 RD and VD Roof fans Installation and Operating Instructions EN...

Страница 29: ...13 RD and VD Roof fans Installation and Operating Instructions Notes EN...

Страница 30: ...14 RD and VD Roof fans Installation and Operating Instructions Notes...

Страница 31: ...15 RD and VD Roof fans Installation and Operating Instructions Notes...

Страница 32: ...IOS Ventilatoren GmbH Co KG Lupfenstra e 8 78056 VS Schwenningen F HELIOS Ventilateurs Le Carr des Aviateurs 157 av Charles Floquet 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG Tannstrasse 4...

Отзывы: