– Roof fans

Installation and Operating Instructions

–  The roof fans RD/VD.. EX are designed as components of a 

stationary

 ventilation system. They may only be ope-

rated when installed as intended and the safety by protective installations and the construction according to DIN EN 
14986 required explosion protection measures are guaranteed.

–  According to DIN EN 14986 fans are not to be regarded as absolutely gas tight. The same explosion-proof zone is  

valid for inside and outside!

– 

The fan must only be used for its intended purpose!

–  The transportation of solids or solid particles in the medium as well as fluids is not permitted.
–  Air flow media which attack the materials of the fan are not permitted.
–  The fan is not suitable for handling dusty media. Deposits of dust in the fan casing and/or impellers are not
  permitted. If there is a risk of dust deposits, an air purifier must be provided.
–  The fan must not be connected to a smoke gas duct.

–  The air flow must not contain any solid or liquid substances, which could settle on the motor or impeller and  
    thus create an ignitable surface! If necessary, a suitable filter must be used (e.g. synthetic fibre min. G4)  
  and any chips must be vacuumed.
– The suction-side intake of rust particles (iron oxide) must be prevented. In this respect, the fan must be 

checked for any rust film that could settle on the motor or impeller and thus create an ignitable surface by 
regular inspection. A six-monthly inspection is required to remove any adhesions.

–  The temperature class on the type plate must correspond to the ignition temperature of the gas that may be present  

or the fan must meet a higher temperature class.

– 

The fan may only be operated within the specified performance curve range so that a sufficient cooling is

  ensured. The use beyond the range of the performance curve is not permitted!

1.9  Performance data

The motor type plate informs about the electrical data, these must be coordinated with the local supply network. The
fan performances* were determined on a test stand according to DIN EN ISO 5801:2010-12; they are valid for the 
rated speed and standard execution using a bell mouth without safety guard with unhindered inflow and outflow. 
Diverging executions and adverse installation and operation conditions can lead to a reduction of performance. For 
explosion-proof fans minimum air gaps between casing and impeller are required.

1.10  Sound levels

The sound level* also refers to the configuration in chapter 3.1. Casing vibrations, unfavourable operating conditions 
etc. can lead to an increase of the given data published in the catalogue. Data relating to certain distances (1, 2, 4 m) 
are valid for freefield conditions. The sound levels published in the catalogue can differ considerably after installation as 
sound pressure levels depend on the absorption capacity on the room, the place of installation and other fac tors.

2.0  Safety information for explosion-proof fans

Use, connection and operation for explosion-proof fans underlie special regulations; in case of doubt further inquiry is
necessary. Helios explosion-proof fans are in accordance with the specification ATEX, Directive 2014/34/EU ( 
Equipment Safety Act). For the evaluation of the explosive area an allocation into zones is necessary by the operator.
Only fans with adequate, for the respective zone certified product category may be used. Further information see 
relevant standards and wordings of law.

– 

Before any maintenance or installation work or before opening the terminal compartment, the device is to 
be fully isolated from the power supply and secured against unintended restart! The electrical connection 
must be carried out only by a qualified electrician in accordance with the following wiring diagrams!

–  Compliance with the EMC Directive refers only to this fan when it is directly connected to the public grid. If the fan
  is integrated into a system or supplemented with other components and operated, the manufacturer or operator is
  responsible for compliance with the EMC Directive.
–  Abnormally frequent on/off switching is not permitted. 
– Every motor must have an 

approved PTC-resistor trip device

 of category II (2)G, see EU Directive 2014/34/

EU (  Equipment Safety Act), with a reset lock so that there is no automatic resetting after a loss of con-

trol voltage and voltage restoration. Please observe the special regulations accompanying these units.

–  Intake or entering of foreign objects in the fan has to be avoided by using protection devices (EN 60529) to IP 20
  resp. with a mesh width of not more than 12 mm. It would also cause electrical discharge and / or sparks.
– 

The compliance of the head gap (the gap between blade tip and casing) represents for explosion protection 
an extremely important feature. This can e.g. be affected by external influences on the casing. Therefore, 
the casing may not be deformed during the assembly.

 

Maintaining the required gap, at any point of the cir-

cumference is to be secured by regular control!

 

–  To conform the operational safety, a vibration control is to be carried out in regular intervals! Alternatively, it is advis 

able to install a vibration monitoring in Ex-version on site. This must take the system out of service when exceeding 
the limits. The permissible vibration limits according to ISO 14694 are shown in chapter 3.3.

–  The planners and operators must ensure easy access for inspection and cleaning work! 
–  The operator is responsible for compliance with all installation-related safety.
–  A uniform inflow and a free discharge must be ensured.
–  Upstream and downstream components or those that are directly in the air stream must not have unprotected alu-

minium or steel surfaces. According to DIN EN 14986 no paint containing iron oxide may be used due to the risk  
of thermite reaction (EN 1127-1).

–  If hazards are identified by lightning, the systems must be protected by suitable lightning protection measures.
–  Equipment must stand in a sufficient safe distance to transmitters or be protected by suitable shielding.
–  The regulations to avoid danger of ignition due to electrostatic discharges (TRGS 727) must be implemented.

ATTENTION

 

ATTENTION

 

ATTENTION

 

ATTENTION

 

* (Performance & sound data from the
  currently valid Helios publications and the
 internet)

ATTENTION

 

m

     EN    

CHAPTER 2 

SAFETY INFORMATION 

WARNING

 

m

Содержание RDD 200/4 EX

Страница 1: ...Explosionsgesch tzte Baureihen Explosion proof series RD VD Dachventilatoren Roof fans DE Helios Ventilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS EN...

Страница 2: ...ND WARTUNG Seite 5 4 0 Instandhaltung und Wartung Seite 5 4 1 Reinigung Seite 6 4 2 Hinweise St rungsursachen Seite 6 4 3 Ersatzteile Seite 7 4 4 Stilllegen und Entsorgen Seite 7 KAPITEL 5 TECHNISCHE...

Страница 3: ...s durch trockene luft und staubdichte Verpackung Kunst stoff beutel mit Trockenmittel und Feuchtigkeits in di ka to ren Der Lager ort muss ersch tterungsfrei wassergesch tzt und frei von Temperatur sc...

Страница 4: ...chen Geh use und Laufrad erforderlich 1 10 Ger uschangaben Die Ger uschangaben beziehen sich auf die unter Kapitel 3 1 beschriebene Anordnung Geh usevariationen un g nstige Betriebsbedingungen etc k n...

Страница 5: ...uverh ltnisse kann ein Ber hrungsschutz saugseitig erforderlich sein Ventilatoren die durch ihre Einbauweise z B Anschluss an L ftungskan le gesch tzt sind ben tigen kein Schutzgitter wenn die Anlage...

Страница 6: ...stabstand von 1 m zum Ventilator einzuhalten Der Ventilator muss f r Reinigungs und Wartungszwecke leicht zug nglich sein insbesondere der Klemmenkasten Revisionsschalter Das Geh use darf bei der Mont...

Страница 7: ...h tung Drehrichtung des Laufrades pr fen durch kurzzeitiges Einschalten beim Pr fen der Drehrichtung eine Schutzbrille tragen Stromaufnahme mit Leistungsschildangabe vergleichen Motorschutzeinrichtung...

Страница 8: ...ntilators pr fen Zu und Abstr mung pr fen freihalten falsche Spannung Anschluss pr fen ndern Lagersch den Lager durch Hersteller ersetzen lassen Verschmutzung reinigen unzureichende Nachstr mung Nachs...

Страница 9: ...X D B C LK Y Baureihe VD 180 710 Vertikal ausblasend A B LK Y C D E H G elektrischer Anschluss X VD 180 320 245 213 6 x M6 10 309 30 175 56 Klemmen kasten VD 200 425 330 259 405 249 50 VD 225 50 VD 2...

Страница 10: ...lasse Z ndschutzart des Motors Kennzeichnung Herstelljahr Art Nr SNR Seriennummer und PC Produktionscode Nummer identifizieren den Ventilator eindeutig 5 2 Motortypenschild Eine Kopie des Motortypensc...

Страница 11: ...Farbcode nach IEC 757 U BN br braun brown V GY gr grau grey W BK sw schwarz black TP WH ws wei white PE YE GN ge gn gelb gr n yellow green TP TP 1 2 L3 L2 L1 L1 L2 L3 TP PE TP L1 L2 TP TP 3 Motor mit...

Страница 12: ...hluss Verlegung nach VDE JA 3 Mindestluftspalt gepr ft JA Wert 4 Freier Lauf des Laufrades gepr ft JA 5 Stromaufnahme gemessen vgl mit Typenschild JA Wert 6 F rder und Drehrichtung gepr ft JA 7 Schwin...

Страница 13: ...7 Fehlerschleifen Impedanz TN System oder Erdungswiderstand IT System ausreichend 8 Isolationswiderstand ist ausreichend 9 Die automatische elektrische Schutzeinrichtung spricht in zul ssigen Grenzwer...

Страница 14: ...12 RD und VD Dachventilatoren Montage und Betriebsvorschrift DE...

Страница 15: ...13 RD und VD Dachventilatoren Montage und Betriebsvorschrift Notizen DE...

Страница 16: ...eration Page 5 CHAPTER 4 INSPECTION AND MAINTENANCE Page 5 4 0 Inspection and maintenance Page 5 4 1 Cleaning Page 6 4 2 Information Fault causes Page 6 4 3 Spare parts Page 7 4 4 Put out of service a...

Страница 17: ...oisture indicators The storage place must be water proof vibration free and free of temperature variations The storage temperature of 20 C to 40 C must not be exceeded When storing for several months...

Страница 18: ...inquiry is necessary Helios explosion proof fans are in accordance with the specification ATEX Directive 2014 34 EU Equipment Safety Act For the evaluation of the explosive area an allocation into zo...

Страница 19: ...ull your fingers arms in Only operate with mounted safety devices Do not put objects into the rotating impeller Risk of damage The roof fans have a fixed direction of motor rotation which is marked on...

Страница 20: ...observed The fan must be easily accessible for cle aning and maintenance purposes particularly the terminal box isolator switch The casing must not be deformed or warped during installation minimum ai...

Страница 21: ...ller by switching on for a short time when checking the direction of rotation wear protective goggles compare current consumption with data on the rating plate test functioning of motor protection dev...

Страница 22: ...Supply line insulation damaged Replace supply lines Motor protection switch triggered Tight bearing Have bearing replaced by manufacturer Impeller touching Clean have impeller replaced by manufactu r...

Страница 23: ...0 710 Vertikal ausblasend A B LK Y C D E H G elektrischer Anschluss X VD 180 320 245 213 6 x M6 10 309 30 175 56 Klemmen kasten VD 200 425 330 259 405 249 50 VD 225 50 VD 250 580 450 286 450 279 VD 31...

Страница 24: ...f protection of the motor Classification Year of manufacture Art Nr Ref no SNR serial number and PC production code number identify clearly the fan 5 2 Motor type plate A copy of the motor type plate...

Страница 25: ...ode nach IEC 757 U BN br braun brown V GY gr grau grey W BK sw schwarz black TP WH ws wei white PE YE GN ge gn gelb gr n yellow green TP TP 1 2 L3 L2 L1 L1 L2 L3 TP PE TP L1 L2 TP TP 3 Motor mit TP KL...

Страница 26: ...on to VDE YES 3 Minimum air gap checked YES Value 4 Unhindered running of impeller checked YES 5 Current consumption measured YES Value compare with type plate 6 Airflow direction and direction of rot...

Страница 27: ...isfactory physical check visual check 7 Fault loop impedanz TN system or earthing resistance IT system satisfactory 8 Isolation resistance is satisfactory 9 Automatic electrical protective devices ope...

Страница 28: ...12 RD and VD Roof fans Installation and Operating Instructions EN...

Страница 29: ...13 RD and VD Roof fans Installation and Operating Instructions Notes EN...

Страница 30: ...14 RD and VD Roof fans Installation and Operating Instructions Notes...

Страница 31: ...15 RD and VD Roof fans Installation and Operating Instructions Notes...

Страница 32: ...IOS Ventilatoren GmbH Co KG Lupfenstra e 8 78056 VS Schwenningen F HELIOS Ventilateurs Le Carr des Aviateurs 157 av Charles Floquet 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG Tannstrasse 4...

Отзывы: