16
Fan unit ELS EC..
Installation and Operating Instructions
CHAPTER 8
SERVICING AND
MAINTENANCE
8.0 Service work instructions
m
The safety instructions specified in section 1.2 must be observed!
Contaminated and humid air can affect constant functional reliability. A periodical functional inspection of the back-
draught shutter is recommended. With regard to units with a fire protection damper, the corresponding points of the
relevant approval must be observed. With regard to units with integrated start-up delay and overrun, it must be ensured
that there is a delayed start after activation and an overrun corresponding to the overrun time after deactivation.
8.1 Disassembly of fan unit
m
The safety instructions specified in section 1.2 must be observed!
m
The unit must be fully isolated from the power supply before all maintenance and installation work and
before opening the terminal compartment!
m
DANGER
Fig.24
ä
Release
catch!
Pin
ù
Remove filter!
Pull!
Fig.26
1.
Unlock snap-in hooks with finger!
2.
3.
Fig.25
Fig.27
ò
Loosen screw!
Fig.28
Remove unit
at the lugs!
ò
ò
ù
ò
Fan unit
ù
Grille with hinged facade cover
– with filter holder and filter cleaning indicator
ä
Permanent filter
EN
Содержание 6355
Страница 23: ...21 Ventilatoreinsatz ELS EC Montage und Betriebsvorschrift DE ...
Страница 24: ...22 Ventilatoreinsatz ELS EC Montage und Betriebsvorschrift DE ...
Страница 47: ...21 Fan unit ELS EC Installation and Operating Instructions EN ...
Страница 48: ...22 Fan unit ELS EC Installation and Operating Instructions EN ...
Страница 50: ...24 Fan unit ELS EC Installation and Operating Instructions EN ...
Страница 51: ...25 Fan unit ELS EC Installation and Operating Instructions EN ...