15 Ordering Specifications
52
HELENOS V
15
Ordering Specifications
15.1
General
To know which informations we need, we have made a special order information for
digital governors. It has the No. DG 96 012-d. This form has to be filled in and send to
HEINZMANN together with the order.
15.2
Cable Length
It is of advantage to obtain the harness together with the governor.
It is not possible to use all signals simultaneous because some inputs and
outputs of the governor have various options depending on the application.
Version of Control Unit:
with plugs (IP55)
with terminal strip (IP00)
Version of Actuator:
with plug (IP55)
with terminal strip (IP00)
a) L1 = Control Unit - Power Supply
L 1
Control unit - power supply
............. cm
Cable size
up to 15 m
2 x 2.50 mm²
over 15 - 30 m
2 x 4.00 mm²
b) L2 = Control Unit - Actuator
L 2.1 Control unit - actuator (feedback)
............. cm 3 x 0,75 mm² shielded
L 2.2 Control unit - actuator (power)
............. cm
Cable size
up to 10 m
2 x 2.50 mm²
over 10 - 20 m
2 x 4.00 mm²
over 20 - 30 m
2 x 6.00 mm²