9 Control Unit DC 2005DP.2 - 01 up to DC 2040DP.2 - 01
HELENOS V
21
9
Control Unit DC 2005DP.2 - 01 up to DC 2040DP.2 - 01
9.1
Specification
9.1.1
General
Supply Voltage
24 V DC (12 V DC)
Maximum Voltage
35 V DC
Minimum Voltage
18 V DC (9 V DC)
Maximum Ripple Voltage
maximum 10 % with 100 Hz
Current Consumption
approx. 200 mA + current of actuator
Permissible voltage dip at
maximum current consumption
max. 10 % in Control unit
Fuse protection of governor
16 A
Storing Temperature
-55°C up to +85°C
Operating Temperature
-40°C up to +70°C
Humidity
up to 98% at 55°C,
Shock
50 g, 11 ms- half-sine wave
Protection grade
DC ...2 - 01 - 00
IP 00
DC ...2 - 01 - 55
IP 55
Weight
DC ...2 - 01 - 00
approx. 1.2 kg
DC ...2 - 01 - 55
approx. 3 kg
Insulation resistance
> 1 MOhm at 48 V DC