HeatStar HS125KT Скачать руководство пользователя страница 4

4

Kerosene Forced Air Heater

Operating Instructions and Owner’s Manual

a. Install one of the cotter pins into the hole on one end of 

axle.

b. Slide the large washer, then wheel onto the axle next to the 

cotter pin.

c. Slide the spacer onto the axle next to the wheel.
d. Slide the partially assembled axle through the wheel 

support frame.

e. Slide the spacer onto the axle next to the wheel support.
f.  Slide the wheel then large washer onto the axle and hold in 

place with the remaining cotter pin.

g. Install the caps over the larger washers to finish the wheel 

assembly.

2.  Position the heater on the wheel support frame assembly 

with the exit opposite the wheels.

3.  Use eight screws and nuts to attach the handles to the top 

of the tank flange. The screws will go through the handles, 
tank flange and wheel support frame. Install the nuts and 
finger tight only until all nuts are installed.

4.  Tighten all the nuts.
5.  Attach cord caddies to handles using No. (4) & No. (5) 

screws and nuts.

PREPARING FOR OPERATION

1.  Check the heater for possible shipping damage. If any is 

found, 

immediately

 contact the manufacturer at 

 

800-251-0001.

2.  Follow all of the “Precautions”. 
3.  Fill the fuel tank with clean kerosene. In extremely cold 

weather, condensation may develop in the tank and it is 
recommended that a tablespoon of de-icer be added for 
each gallon (4 liters) of fuel in the tank. When filling the 
heater, use at least 2 gallons (8 liters) of fuel. Be sure heater 
is level and do not overfill. Use a funnel or can with a long 
fill spout.

IMPORTANT: Before filling fuel tank the first time or after ex

-

tended storage periods, drain the fuel tank of any moisture 
or condensation.

4.  Locate heater at a safe distance from combustible materials. 

Models 50 & 75 are not suitable for use on wood floors or 
other combustible materials. When used, the heater should 
rest on suitable insulating material at least 1 inch thick and 
extending 3 ft. or more beyond the heater in all directions.

HEATER START UP

1. 

HS50K:

 Plug the heater into a grounded 115V, 60 Hz, 1 Ø 

outlet.

HS75KT, HS125KT, HS175KT & HS210KT:

 

Turn thermostat 

to lowest setting, make sure “On/Off” switch is “Off”. Plug 
the heater into a grounded 115V, 60 Hz, 1 Ø outlet. Turn 
thermostat to highest setting. Start heater by pushing toggle 
switch to “On” position (light signifies switch is in “ON” 
position). Adjust thermostat to desired setting. Heater will 
cycle on/off as heat is required.
EXTENSION CORD REQUIREMENTS: Up to 100’ (30.5m) use 
16 awg. conductor. 101’ - 200’ (30.5 - 61.0m) use 14 awg. 
conductor.

For all models: 

•  In cold weather (below 10° F), starting may be improved by 

holding a finger over the vent hole of the pump adjustment 
screw until the heater starts. 

•  This unit is equipped with an interrupt circuit. The reset is 

integrated into the “On/Off” switch. If the unit does not 
start, toggle the switch to “Off”, wait 5 min. and toggle 

the switch to “On”.

HEATER SHUT DOWN

1. 

HS50K: 

Unplug heater from power source.

 

HS75KT, HS125KT, HS175KT & HS210KT: 

Push “On/Off” 

switch to “Off” position. For extended shutdown, unplug hea-
ter from power source.

RESTART AFTER SAFETY SHUTDOWN

  

(

HS50K, HS75KT, HS125KT, HS175KT & HS210KT) 

See page 6.

HS50K - Unplug unit. Wait 5 minutes. Plug back in.
HS75KT, HS125KT, HS175KT & HS210KT - Toggle switch to “OFF” 

position, wait 5 minutes. Restart.

MAINTENANCE AND STORAGE

WARNING.

 To prevent personal injury, unplug the heater from the 

wall outlet before servicing. 
For maximum efficiency and trouble-free service, make the 
following periodic maintenance, cleaning and inspections.

ADJUSTING PUMP PRESSURE 

Due to varying fuel viscosities and normal component wear the 
pump pressure on this heater may need to be adjusted.  

ADJUSTMENT PROCEDURE:

1. 

Fill fuel tank.

2.  Start heater.

3. 

Locate the fuel pressure adjustment screw (ref. #26) in the 
exploded parts drawing.  The pressure adjustment screw 
is located at the rear of the heater, in the air filter housing 
cover (slotted adjustment screw approx.10 o’clock position). 

4. 

The plug directly under the adjustment screw can be used to 
install a pressure gauge.  It is not a second adjustment screw.

5. 

Using a flat bladed screw driver, turn the pump pressure 
adjustment screw clockwise to increase pump pressure and/
or counter-clockwise to decrease pump pressure.  Base pump 
pressures can be found in the specifications chart on page 3 
of the “Operating Instructions and Owners’ Manual”.

6. 

For best results, the nose cone in the combustion chamber 
should be cherry red with no dark spots and the flame 
should not extend beyond the nose cone.

IMPROPER PRESSURE ADJUSTMENT

Problem: 

   Heater does not have a strong consistent flame.

 

 

Heater smokes and spits raw fuel.

 

 

Nose cone does not get cherry red.

Adjustment:

 Pump pressure is too low.  

 

 

Turn adjustment screw clockwise to increase pump  

 

 

pressure.

Problem:

 

Flame extends beyond the end of the heater.

Adjustment:

 Pump pressure is too high. 

 

 

Turn adjustment screw counter clockwise to  

 

 

decrease pump pressure.

DAILY SCHEDULE

1.  GENERAL. Make general visual inspection of heater for loose 

or damaged parts. Check nuts and bolts to insure against 

Содержание HS125KT

Страница 1: ...ity of this or any other appliance Service must be performed by a qualified service agency This is an unvented portable heater It uses air oxygen from the area in which it is used Adequate combustion...

Страница 2: ...DAMAGE FROM HAZARDS OF FIRE EXPLOSION BURN ASPHYXIATION CARBON MONOX IDE POISONING AND OR ELECTRICAL SHOCK ONLY PERSONS WHO CAN UNDERSTAND AND FOLLOW THE INSTRUCTIONS SHOULD USE OR SERVICE THIS HEATE...

Страница 3: ...with the safety precautions and instructions and of the hazards involved SAFETY PRECAUTIONS 1 Recommended for use with No 1 K kerosene fuel Factory tested for use with No 2 K kerosene No 1 or No 2 Di...

Страница 4: ...SION CORD REQUIREMENTS Up to 100 30 5m use 16 awg conductor 101 200 30 5 61 0m use 14 awg conductor For all models In cold weather below 10 F starting may be improved by holding a finger over the vent...

Страница 5: ...If this occurs replace the fuel nozzle 5 FUEL TANK Clean twice a season during frequently used periods clean twice a month Drain and flush the fuel tank with clean fuel oil ANNUAL SCHEDULE 1 AIR OUTP...

Страница 6: ...n electrode probes 2 3 3 mm 4 Still no spark replace igniter assembly 5 Replace oil flame control assembly Abnormal Motor Operation 1 Motor speed too low Motor should operate at 3450rpm Motor overheat...

Страница 7: ...ked A heater which is not working right must be repaired but only by a trained experienced service person 18AWG BLUE THERMOSTAT 18AWG PURPLE COM1 I2 I1 M2 M1 L N 18AWG PURPLE 18AWG GRN 18AWG BLK 18AWG...

Страница 8: ...r office hours are 8 00 AM 5 00 PM EST Monday through Friday Please include the model number date of purchase and description of problem in all communication LIMITED WARRANTY Enerco Technical Products...

Страница 9: ...un fournisseur de services d entretien qualifi Cet appareil de chauffage portatif n est pas ventil Il utilise l oxyg ne de l air ambiant Une circulation d air ad quate doit tre assur e pour la combust...

Страница 10: ...LURE D ASPHYXIE D INTOXICATION AU MONOXYDE DE CARBONE OU D LECTROCUTION SEULES LES PERSONNES APTES COMPRENDRE ET RESPECTER LES INSTRUCTIONS DEVRAIENT UTILISER OU EFFECTUER L ENTRETIEN DE CET APPAREIL...

Страница 11: ...e chauffage doit fonctionner en pr sence d autres personnes l utilisateur est responsable d informer ces derni res des instructions et pr cautions li es la s curit et de les avertir des dangers inh re...

Страница 12: ...s des p riodes d entreposage prolong es enlevez en la condensation 4 Placez l appareil de chauffage une distance s curitaire des mat riaux combustibles Les mod les 50 et 75 ne sont pas con us pour tre...

Страница 13: ...es avec un chiffon sec et propre Inspectez ces endroits pour vous assurer que toute mati re trang re a t enlev e particuli rement autour du br leur et de la zone de combustion 3 CELLULE AU CADMIUM Net...

Страница 14: ...e 4 2 V rifiez le c blage vers l allumeur selon le sch ma de c blage du pr sent guide 3 V rifiez l cart entre les pointes d lectrode 2 3 3 mm 4 S il n y a toujours pas d tincelle remplacez l allumeur...

Страница 15: ...r Si l appareil de chauffage ne fonctionne pas correctement il doit tre r par uniquement par un technicien qualifi COM1 I2 I1 M2 M1 L N 1 3 2 H2 H1 VRT AWG 18 JAUNE AWG 18 NOIR AWG 18 JAUNE AWG 18 BLE...

Страница 16: ...10 Kerosene Forced Air Heater Operating Instructions and Owner s Manual PAGE LEFT INTENTIONALLY BLANK...

Страница 17: ...enerco com Nos heures d ouverture sont de 8 h 00 17 h HNE du lundi au vendredi Veuillez indiquer le num ro du mod le la date d achat et la description du probl me dans toutes vos communications avec n...

Страница 18: ...to El mantenimiento debe ser realizado por una agencia de reparaci n calificada Este calentador port til no tiene una fuente propia de ventilaci n Utiliza el aire ox geno del rea en la cual se emplea...

Страница 19: ...O DE INCENDIO EXPLOSI N QUEMADURAS ASFIXIA ENVENENAMIENTO CON MON XIDO DE CARBONO Y O DESCARGAS EL CTRICAS SOLO LAS PERSONAS QUE ENTIENDAN Y PUEDAN SEGUIR LAS INSTRUCCIONES DEBEN USAR O MANTENER ESTE...

Страница 20: ...as o la ignici n de su ropa No tocar Mantener alejado de los ni os la ropa y el combustible 8 Instale el calentador de forma tal que no est directamente expuesto a salpicaduras de agua lluvia o agua 9...

Страница 21: ...alentador realizar ciclos de encendido apagado a medida que se necesite calor REQUISITOS DEL CABLE DE EXTENSI N hasta 100 30 5 m use un conductor CAE 16 101 200 30 5 61 0 m use un conductor CAE 14 Par...

Страница 22: ...tible y aire y olor y humo en exceso Si esto sucede reemplace el pico de combustible 5 TANQUE DE COMBUSTIBLE L mpielo dos veces por temporada durante per odos de uso frecuente l mpielo dos veces por m...

Страница 23: ...iagrama Verifique los requisitos en la p gina 4 2 Verifique el cableado al encendedor seg n el esquema de cableado en el manual 3 Verifique el espacio entre las sondas de electrodos 2 3 3 mm 4 A n no...

Страница 24: ...rectamente debe ser reparado pero solo por un t cnico de mantenimiento capacitado y experimentado I2 I1 M2 M1 L N 1 3 2 H2 H1 18 AWG VERDE 18 AWG NEGRO 18 AWG BLANCO LLAVE DE ENCENDIDO JUEGO DE CABLES...

Страница 25: ...10 Kerosene Forced Air Heater Operating Instructions and Owner s Manual PAGE LEFT INTENTIONALLY BLANK...

Страница 26: ...ajo es de 8 00 a m a 5 00 p m hora del este de lunes a viernes Incluya el n mero de modelo la fecha de compra y la descripci n del problema en todas sus comunicaciones GARANT A LIMITADA Enerco Technic...

Отзывы: