Heat&GloGlo 6000CF-OAK-IPI Скачать руководство пользователя страница 45

45

Heat & Glo  •  6000CF-OAK-IPI  •  2092-900  Rev. 

I

  •  1/06

Inspect

Maintenance Tasks

Doors, Surrounds

and Fronts

1.

  Assess condition of screen and replace as necessary.    

Recommend addition of screen

if one is not present.

2.

  Inspect for scratches, dents or other damage and repair as necessary.

3.

  Verify no obstructions to airflow through the louvers.

4.

  Verify maintenance of proper clearance to combustible household objects.

Gasket Seal, Glass

Assembly and Glass

1.

  Inspect gasket seal and its condition.

2.

  Inspect glass panels for scratches and nicks that can lead to breakage when exposed to

heat.

3. 

Confirm there is no damage to glass or glass frame. Replace as necessary.

4. 

 Verify that latches engage properly, clip studs are not stripped, and glass attachment

components are intact and operating properly. Replace as necessary.

5.   

Clean glass. Replace glass assembly if severely coated with silicate deposits that cannot

be removed.

Valve Compartment

and Firebox Top

1. 

 Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these

areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.

2.

  Remove any foreign objects.

3.

  Verify unobstructed air circulation.

Logs

1.

  Inspect for broken, damaged, or missing logs. Replace as necessary.

2. 

 Verify correct log placement and no flame impingement causing sooting. Correct as

necessary.

Firebox

1.

  Inspect for paint condition, warpage, corrosion or perforation. Sand and repaint as

necessary.

2.

  Replace appliance if firebox has been perforated.

Burner Ignition and

Operation

1. 

 Verify burner is properly secured and aligned with pilot or igniter.

2. 

 Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if

necessary.

3. 

 Replace ember materials with new dime-size and shape pieces. Do not block ports or

obstruct lighting paths.

4.

  Check for smooth lighting and ignition carryover to all ports. Verify there is no ignition delay.

5.

  Inspect for lifting or other flame problems.

6.

  Verify air shutter is clear of dust and debris.

7.

  Inspect orifice for soot, dirt or corrosion.

8.

  Verify manifold and inlet pressures. Adjust regulator as required.

9. 

 Inspect pilot flame strength. Clean or replace orifice as necessary.

10.

  Inspect thermocouple/thermopile or IPI sensor rod for soot, corrosion and deterioration.

Clean with emery cloth or replace as required.

11. 

 Verify millivolt output. Replace as necessary.

Venting

1

.  Inspect venting for blockage or obstruction such as bird nests, leaves, etc.

2.

  Confirm that termination cap remains clear and unobstructed by plants, etc.

3.

  Verify that termination cap clearance to subsequent construction (building additions, decks,

fences or sheds) has been maintained.

4. 

 Inspect for corrosion or separation.

5.

  Verify weather stripping, sealing and flashing remains intact.

6.

  Inspect draft shield to verify it is not bent, damaged or missing.

Remote controls

1.

  Verify operation of remote.

2.

  Replace batteries in remote transmitters and battery-powered receivers.

3.

  Verify batteries have been removed from battery back-up IPI systems to prevent premature

battery failure or leaking.

Содержание 6000CF-OAK-IPI

Страница 1: ...dren in same room as appliance Alert children and adults to hazards of high temperatures Do NOT operate with protective barriers open or removed Keep clothing furniture draperies and other combustible...

Страница 2: ...ce can be found on the rating plate usually located in the control area of the appliance Homeowner Reference Information Heat Glo a of Hearth Home Technologies Inc brand 20802 Kensington Boulevard Lak...

Страница 3: ...tact Information 54 Section 1 Listing and Code Approvals A Appliance Certification 4 B Glass Specifications 4 C BTU Specifications 4 D High Altitude Installations 4 E Non Combustible Materials Specifi...

Страница 4: ...ifice to a smaller size Input rate should be reduced by 4 for each 1000 feet above a 2000 foot elevation in the U S A or 10 for elevations between 2000 and 4500 feet in Canada If the heating value of...

Страница 5: ...ing The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipment p...

Страница 6: ...from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see Figure 3 1 Figure 3 1 Appliance Location...

Страница 7: ...her prevent drafts the wall shield and ceiling firestops should be caulked with high temperature caulk to seal gaps Gas line holes and other openings should be caulked with C Clearances Fire Risk Cons...

Страница 8: ...ther Combustibles above Appliance Figure 3 4 Clearances to Mantel Legs or Wall Projections Acceptable on both sides of opening Note All measurements in inches 1 inch 3 feet MANTEL LEG Top View 7 1 4 7...

Страница 9: ...Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 4 1 Figure 4 2 Minimum Height from Roof to Lowest Discharge Opening Termination Locations 4 Measure horizontal clearances from this surface Meas...

Страница 10: ...nd with an overhang are permitted with the dimensions specified for vinyl or non vinyl siding and soffits 1 There must be 3 feet minimum between termination caps 2 All mechanical air intakes within 10...

Страница 11: ...run A length of straight pipe is allowed between two 450 elbows see Figure 5 1 Figure 5 1 A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams Symbol Descrip...

Страница 12: ...pipe may cause fire WARNING 1 Top Vent Horizontal Termination One Elbow Two Elbows V1 Minimum H1 Maximum 6 inches 152mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7...

Страница 13: ...457 mm 6 ft 1 8 m 1 ft 305 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 2 ft 607 mm 6 ft 1 8 m 2 ft 610 mm 6 ft 1 8 m 2 ft 610 mm 6 ft 1 8 m 4 ft 1 4 m 12 ft 3 7 m 3 ft 914 mm 9 ft 2 7 m 3 ft 914 mm 9 ft 2...

Страница 14: ...t 305 mm 3 ft 914 mm 2 ft 607 mm 6 ft 1 8 m 4 ft 1 2 m 12 ft 3 7 m V1 V2 H1 50 ft 15 2m Max No specific restrictions on this value EXCEPT V1 V2 H1 cannot exceed 50 ft 15 2m V1 6 inches 152 mm Min NOTE...

Страница 15: ...tinued V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum 6 in 152 mm 3 ft 914 mm 3 ft 914 mm 1 ft 305 mm 3 ft 914 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 6 ft 1 8 m 4 ft 1 2 m 12 ft 3 7 m 12 ft 3 7 m H1 H2 17 ft...

Страница 16: ...the shield in place using the four pilot holes pro vided in the part Position the shield so the longest dimension 13 1 2 inch is placed in same direction the elbow is pointing Center the shield direc...

Страница 17: ...e being penetrated is surrounded by noncombusti ble materials such as concrete a hole with diameter one inch greater than the pipe is acceptable B Wall Penetration Framing Figure 6 5 Horizontal Ventin...

Страница 18: ...the vent pipe Installing Attic Shield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling s...

Страница 19: ...d slots The face of the sheetrock ledge assembly and the unit surround should be flush to each other Figure 7 3 Remove the lower access panel to run the electrical and gas lines to the unit see Figure...

Страница 20: ...bs on each side Keep nailing tabs flush with the framing Secure the appliance to the framing by using nails or screws through the nailing tabs Figure 7 4 Proper Positioning Leveling and Securing of Ap...

Страница 21: ...7 8 3 Center the Flue Restrictor on vent and secure in place by using two self tapping screws see Figure 7 8 CHART Vertical Top Vent NG Top Vent LP 4 1 1 No Restrictor 8 2 2 1 2 15 3 3 3 2 20 3 4 3 3...

Страница 22: ...from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 inch If predrilling screw ho...

Страница 23: ...ng the inner and outer flues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be cut to a certain length...

Страница 24: ...of pipe must be supported every 8 feet after the 25 foot maximum unsupported rise The vent support or plumber s strap spaced 120 apart may be used to do this see Figure 8 8 Horizontal Sections Horizon...

Страница 25: ...rom the pipe section see Figure 8 12 Installing the Horizontal Termination Cap Vent termination must not be recessed in the wall Siding may be brought to the edge of the cap base Flash and seal as app...

Страница 26: ...oof Pitch H Min Ft HORIZONTAL OVERHANG VERTICAL WALL TERMINATION CAP 12 X ROOF PITCH IS X 12 LOWEST DISCHARGE OPENING H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING 2 FT MIN 20 INCHES To a...

Страница 27: ...both halves of the storm collar with two screws see Figure 8 15 Wrap the storm collar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to...

Страница 28: ...o the 1 2 inch 13mm control valve inlet If substituting for these components please consult local codes for compliance NOTE The gap between supply piping and gas access hole may be caulked with high t...

Страница 29: ...heck with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve com partment and connected to...

Страница 30: ...irements Wiring for optional accessories should be done now to avoid reconstruction This appliance may be used with a wall switch wall mounted thermostat and or a remote control If using thermostat us...

Страница 31: ...TERMITTENT PILOT IGNITOR IGNITION MODULE 3V ON OFF WALL SWITCH LOW VOLTAGE PLUG IN 3V TRANSFORMER NEUTRAL HOT GROUND FLAME SPARKER SENSOR REMOTE CONTROL SEE NOTE 1 ORG WHT VALVE PIGGYBACK ON OFF SWITC...

Страница 32: ...res to the junction box as shown Add a 1 4 inch insulated female connector to the red switch leg wire route it through the knockout in the face of the junction box and connect to the top fan switch co...

Страница 33: ...y a 300o F minimum sealant Figure 11 2 Mantel Leg or Wall Projections Acceptable on both sides of opening Figure 11 1 Clearances to Mantels or other Combustibles above Appliance SEALANT MATERIAL 0 FIN...

Страница 34: ...ee Ser vice Parts List for appropriate accessories Refer to Section 16 Removing Optional GFK 160A Fan ITEM 1 Remove front from the fireplace see Fig ure 12 1 2 Remove glass assembly from the fire plac...

Страница 35: ...acing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail...

Страница 36: ...LOG 1 SRV385 720 Place the log so that the notches on the bottom of log line up with the grate bars Note There should be about 1 4 gap between the log and the hump on the burner STEP 3 LOG 2 SRV385 7...

Страница 37: ...the slot in the underside of this log Place the log so that this slot fits onto the right metal tab on log 1 Swing the lower end so that it sits in or above the dent on the top of log 2 STEP 6 LOG 5...

Страница 38: ...er up the gap between the sheet rock and the appliance Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that the bottom grille can be lowered...

Страница 39: ...er removed Contact your dealer or Hearth Home Technologies if the barrier is not present or help is needed to properly install one Glass door must be in place when appliance is operating Risk of Combu...

Страница 40: ...r maintenance can cause injury or property dam age Refer to the owner s informa tion manual provided with this ap pliance This appliance needs fresh air for safe operation and must be in stalled so th...

Страница 41: ...nt or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapor...

Страница 42: ...module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC b A shorted or loose connection in wiring configuration or wiring harness Remove and...

Страница 43: ...ch or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is...

Страница 44: ...s Handle glass assembly with care NOTE Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door...

Страница 45: ...t as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for...

Страница 46: ...raming dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions A B C D E F G H I J K L M N O P Q Inches 28 1 2 14 1 4 21 1 2 12 7 8 8 38 6 7 8 2 1 8 21 1 2 32 1 4 36 1 8 41 1 8 7...

Страница 47: ...DVP12A 3 to12 DVP12MI 3 to12 DVP24MI 3 to 24 10 1 2 in 10 7 8 in 45 7 3 8 in 11 3 8 in 1 1 4 in 9 1 4 in 13 1 4 in 1 2 in TYP DVP90 DVP90ST 90 Elbow 10 in 1 in 12 in 14 in 1 in 8 in 6 in 10 in 1 1 2 i...

Страница 48: ...erm Cap Effective Length Effective Length TRAP1 4 1 8 in 5 5 8 in TRAP2 6 3 4 in 10 5 8 in Wall Shield Firestop Heat Shield DVP TRAP1 DVP TRAPK1 Horizontal Termination Cap Kit DVP90ST Wall Shield Fire...

Страница 49: ...13 1 4 in 24 5 8 in 27 1 2 in RF6M Roof Flashing Multi pak 31 in 24 5 8 in 13 1 4 in RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 5 in 13 3 4 in 7 1 4 in 5 1 4 in 12 1 2 in DV...

Страница 50: ...pressly authorized and approved by HEAT GLO in writing 6 Anydamages caused by environmental conditions inadequate ventilation or drafting caused by tight sealing construction of th estructure air hand...

Страница 51: ...ontact your Heat Glo dealer with any questions or concerns For the number of your nearest Heat Glo dealer please call 1 888 427 3973 Printed in U S A Copyright 2006 DO NOT DISCARD THIS MANUAL CAUTION...

Отзывы: