Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13
34
A tap is provided on the outlet side of the gas control for a
test gauge connection to measure the manifold pressure.
To measure inlet pressure, provisions must be made to
attach a test gauge to the tap immediately upstream of
the gas supply connection to the fireplace.
The fireplace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of 60 mbar.
If the fireplace must be isolated from the gas supply
piping system by closing an individual shut-off valve, it
must be of the handle-less type.
Pressure requirements for Heat & Glo gas
fireplaces are shown in the table below.
Step 7
Gas Pressure
Requirements
Natural Gas
Propane
Butane
Natural Gas
(G20)
(G31)
(G30)
(G25)
Inlet Pressure
20 mbar
30 or 50 mbar 30 or 50 mbar
25 mbar
Manifold Pressure
4 - 8.7 mbar 15.7 - 25 mbar 15.7 - 25 mbar 4 - 8.7 mbar
Gas Rate
.54
m3
/
h
.24
m3
/
h
.16
m3
/
h
.54
m3
/
h
Max. Input (NETCV)
6.0 kW
5.4 kW
5.2 kW
5.0 kW
Burner Injector
DMS 44
DMS 55
DMS 56
DMS 42
Pilot Injector
51
30
30
51
Step 8
wiring the
Fireplace
Optional Accessories
Optional remote control kits require that 230 VAC be
wired to the factory installed junction box before the
fireplace is permanently installed.
!
wARNING: DO NOT CONNECT 230 vAC
TO THE GAS CONTROL vALvE OR THE
APPLIANCE wILL MALFUNCTION AND THE
vALvE wILL BE DESTROYED
.
NOTE: Electrical wiring must be installed by a
competent electrician.
Appliance Requirements
• This appliance
DOES NOT
require 230 VAC to
operate.
wall Switch
Position the wall switch in the desired position on a wall.
Run a maximum of 780 cm or less length of 0.102 cm
diameter minimum wire and connect it to the fireplace
ON/OFF switch pigtails.