Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13
27
Figure 40 Securing vertical Pipe Sections
Figure 41 Securing Horizontal Pipe Sections
H. Securing the Flue Pipe Sections (DVP and
SLP Pipe)
• Vertical runs of DVP pipe must be supported every 2.44
m after the 7.62 m maximum unsupported rise.
• Vertical runs of SLP pipe must be supported every 2.44 m.
• Horizontal sections must be supported every 1.52 m.
• Flue pipe supports or plumbers strap (spaced 120º apart)
may be used to support. See figures 40 and 41.
• Wall shield firestops may be used to provide horizontal
support.
• SLP ceiling firestops have tabs that may be used to
provide vertical support.
warNiNG! risk of fire, explosion or asphyxiation!
Improper support may allow flue pipe to sag and sepa
-
rate. Use flue pipe run supports and connect flue pipe
sections per installation instructions.
DO NOT
allow flue
pipe to sag below connection point to appliance.