Heat & Glo • SL-350TRS-CE-D • 2033-900 Rev. V • 3/13
12
HORIZONTAL
TERMINATION
WALL FIRESTOP
90 DEGREE
ELBOW
VERTICAL
TERMINATION
STORM COLLAR
ROOF FLASHING
HORIZONTAL PIPE
SUPPORT
PIPE LENGTH
WALL BRACKET
CEILING
FIRESTOP
DVP-SERIES
SLP SERIES
DVP-TRAP
DVP-TVHW
Flue system termination kits
SLP-TVHW
SLP-TRAP2
Figure 5. Flue Components and Terminations
A. Flue System Approvals
These models have flue starting collars on both the top and
the back of the unit. Depending upon the installation, decide
which ONE set of starting collars will be used to attach the
flue system. The starting collar sealing cap must remain on
the starting collar NOT used.
These models use SLP series, direct flue components when
using the
TOP
flue collars and DVP SERIES direct flue
components when using the
REAR
flue collars.
Step 3
Installing the
Flue System
Approved flue system components are labeled for
identification.
NO OTHER FLUEING SYSTEMS OR
COMPONENTS MAY BE USED
. Detailed installation
instructions are included with each flue termination kit and
should be used in conjunction with this
Installers Guide
.
Figure 4 shows flue system components and terminations.
Identifying Flue Components
The flue systems installed on this gas fireplace may include
one, two, or three 90°
elbow assemblies. The relationships
of vertical rise to horizontal run in flue configurations using
90° elbows
MUST BE
strictly adhered to. The rise to run
relationships are shown in the flueing drawings and tables on the
next several pages.
NOTE:
Two 45° elbows may be used in place of one 90°
elbow. You
MUST
always maintain the
MAXIMUM
and
MINIMUM
rise-to-run ratios in the flue system when using
45° elbows.
wARNING: YOU MUST NOT MIX DvP SERIES
AND SLP SERIES COMPONENTS IN ANY
FLUE SYSTEM CONFIGURATION.
!