Heat & Glo • SL-750TRS-IPI-D, SL-550TRS-IPI-D, SL350TRS-C • InD • 2065-985 Rev. o • 3/07
11
V
= VENT TERMINAL
X
= AIR SUPPLY INLET
= AREA WHERE TERMINAL IS NOT PERMITTED
Figure 4.4 Minimum Clearances for Termination
A
= 12 inches ...............clearances above grade, veranda,
porch, deck or balcony
B =
12
inches
...............clearances to window or door
that may be opened, or to perma-
nently closed window. (Glass)
D*
= 18 inches ...............vertical clearance to unventilated
sof
¿
t or to ventilated sof
¿
t located
above the terminal
*30 inches ..............for vinyl clad sof
¿
ts and below
electrical service
F
= 9 inches ................clearance to outside corner
G
= 6 inches .................clearance to inside corner
H
= 3 ft. (Canada) ........not to be installed above a gas
meter/regulator assembly within 3
feet (90cm) horizontally from the
center-line of the regulator
I
= 3 ft. .......................clearance to gas service regulator
vent outlet
J
= 9 inches (U.S.A.)
12 inches (Canada) clearance to non-mechanical
air supply inlet to building or the
combustion air inlet to any other
appliance
K
= 3 ft. (U.S.A.)
6 ft. (Canada) ...........clearance to a mechanical (pow-
ered) air supply inlet
L** = 7
ft.
..........................c l e a r a n c e a b o v e p a v e d
sidewalk or a paved driveway
located on
public
property
M*** = 18 inches.................clearance under veranda, porch,
deck, balcony or overhang
42
inches
................vinyl
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.
** a vent shall not terminate directly above a sidewalk or paved driveway
which is located between two single family dwellings and serves both
dwellings.
*** only permitted if veranda, porch, deck or balcony is fully open on a
minimum of 2 sides beneath the
À
oor, or meets Note 2.
NOTE 1
: On private property where termination is less than 7 feet above
a sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See vents components page)
NOTE 2
: Termination in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions speci
¿
ed for
vinyl or non-vinyl siding and sof
¿
ts.
1
. There must be 3 feet minimum
between termination caps.
2.
All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap.
3.
All gravity air intakes within 3 feet of a termination cap must be a
minimum of 1 foot below the termination cap.
(See Note 1)
(See Note 1)
(See Note 2)
NOTE 3
: Local codes or regulations may require different
clearances.
NOTE 4:
Termination caps may be hot. Consider their proximity to
doors or other traf
¿
c areas.
NOTE 5:
Location of the vent termination must not interfere with
access to the electrical service.
WARNING: In the U.S:
Vent system termination is
NOT
permitted in
screened porches. You must follow side wall, overhang and ground
clearances as stated in the instructions.
In Canada:
Vent system termination is
NOT
permitted in screened
porches. Vent system termination is permitted in porch areas with
two or more sides open. You must follow all side walls, overhang
and ground clearances as stated in the instructions.
Hearth & Home Technologies assumes no responsibility for the
improper performance of the appliance when the venting system
does not meet these requirements.
Q
MIN
= # termination caps x 3 R
MAX
= (2 / # termination caps) x Q
ACTUAL
N
= 6 inches ..................non-vinyl sidewalls
12 inches ................vinyl sidewalls
P =
8
ft.
Alcove Applications
S = 6 inches ...................clearance from sides of elec-
trical service
T = 12 inches ..................clearance above electrical
service
(See Note 5)
(See Note 5)
Electrical
Service
V
S
V
S
V
T
D*
V
M
N
P
R
Q
Q
MIN
R
MAX
1 cap
3 feet
2 x Q
ACTUAL
2 caps
6 feet
1 x Q
ACTUAL
3 caps
9 feet
2/3 x Q
ACTUAL
4 caps
12 feet
1/2 x Q
ACTUAL