MODU-FIRE
®
Forced Draft Gas-Fired Boiler 2500-3000
41
5.8 A
UTO
-
RESET
E
RROR
C
ODES
–
E##
Code ENVI
®
Control Display
Lock-
out
Description
E01 T FLOW OPEN
53
Flow sensor not connected
E02 T RETURN OPEN
54
Return sensor not connected
E03 T FLUE OPEN
59
Flue sensor not connected
E04 T DHW OPEN
57
DHW sensor not connected
E05 T HX OPEN
58
Heat exchanger sensor not connected
E06 HEADER SENSOR OPEN
70
Header sensor on IF board not connected
E11 T FLOW SHORTED
61
Flow sensor shorted
E12 T RETURN SHORTED
62
Return sensor shorted
E13 T FLUE SHORTED
67 Flue
sensor
shorted
E14 T DHW SHORTED
65 DHW
sensor
shorted
E15 T HX SHORTED
66
Heat exchanger sensor shorted
E16 HEADER SENSOR SHORTED
71
Header sensor on IF board shorted
E18 PHASE ERROR
46
Phase and neutral of supply voltage mains are reversed
E19 E2PROM READ ERROR
0
Problems from reading from or writing to E2prom
E20 FLAME ERROR 2
74
False flame detected
E21 LOW FLOW/ILK
73
Low flow or interlock error
E22 WD 50HZ ERROR
45
No earth ground connected or internal hardware error
E23 NET FREQ ERROR
47
Main supply voltage frequency differs more than 2%
from 60HZ
E24 FAULTY EARTH ERROR
48
Faulty earth ground to boiler
E30 FLUE GAS ERROR
39
Flue gas sensor is above setpoint plus differential
E32 RETURN TEMP ERROR
42
Return temperature is above 90 degrees
E34 BLOCKED FLUE ERROR
41
Flue gas outlet is restricted or blocked
E41 REVERSE FLOW ERROR
43
Supply and return temp are reversed
E42 WD COMMUNICATION ERROR
49
Internal hardware error
E44 FLAME CKT FAULT
40
Ionization or flame rod wire is lost
E45 REFHI TOO LO ERROR
35
Internal hardware error
E46 REFHI TOO HI ERROR
36
Internal hardware error
E47 REFLO TOO LO ERROR
37
Internal hardware error
E48 REFLO TOO HI ERROR
38
Internal hardware error
E 49 RAPID RISE HX ERROR BLOCK
51
Heat exchanger temperature rise to rapidly (blocking)
E50 RAPID RISE ERROR BLOCK
72
Flow temperature rise too rapidly (blocking)
E51 RESET BUTTON ERROR
68
Reset button pressed more than 7 times within 1 minute
E52 APPLIANCE SELECTION ERROR
50
Appliance and resistor do not match at start up
E54 IF COMMUNICATION FAILURE
69
No communication with interface board
Содержание 1004905923
Страница 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Страница 31: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 31 Ratio V Adjust at Hi Fire Bias N Adjust at Low Fire ...
Страница 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Страница 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Страница 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Страница 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...