2/25/03
888-2473-001
2-19
WARNING: Disconnect primary power prior to servicing.
Section 2 Installation / Initial Turn-On
ATLAS Series™
mance. Power down and rewire for correct sequence of the AC phases if
required.
2.13.1.2 Setting the Test Load Flow Switch Trip Level
To set the trip level, an external flow meter needs to be attached in series with the
load coolant supply.
Adjust the load coolant supply valve until the meter reads the correct flow
indicated in the table in drawing 843-5550-170
(843-5550-213 for DVL 4300
and DVL 5700).
!
CAUTION:
IN ORDER TO PROTECT THE TEST LOAD, THE LOAD FLOW SWITCH SHOULD
BE SET TO OPEN IF ADEQUATE FLOW IS NOT PROVIDED TO THE LOAD.
Check the Load interlock.
Once the flow rate is correct, press OUPUT to go to the
RF Output screen. This screen displays status of the load interlock (open or closed).
Adjust the flow switch trip level until the GUI displays Load Interlock: Closed.
Verify that the flow switch operates correctly by decreasing the amount of flow
through the load. The interlock should OPEN.
Go back to the nominal flow rate recommended for the test load.
The interlock
should close.
2.13.1.3 Setting the Heat Exchanger Fan Turn ON Temperatures
The two stage thermostat that controls the heat exchanger fan turn on temperatures
were factory set for 32
o
C and 38
o
C. The adjustment dial inside the thermostat,
marked in deg C, controls fan A and is set at 32
o
C, which will switch fan A on
when the coolant temperature reaches 32
o
C. The +/- adjustment knob, next to the
dial, controls the differential when fan B will switch on, which is factory set to
+6
o
C. This will switch fan B on when the coolant temperature reaches 38
o
C.
2.13.1.4 Verifying Pump Switching
In modules with dual pumps, verify that both pumps operate properly by
switching pumps back and forth from the GUI screen. Also verify that correct
flow rate is achieved with either pump active.
Содержание Atlas DVL400
Страница 4: ...888 2473 001 WARNING Disconnect primary power prior to servicing MRH 2...
Страница 6: ......
Страница 8: ......
Страница 11: ......
Страница 12: ......
Страница 100: ...3 40 888 2473 001 2 25 03 WARNING Disconnect primary power prior to servicing Section 3 Operation ATLAS Series...
Страница 146: ...4 46 888 2473 001 2 25 03 WARNING Disconnect primary power prior to servicing Section 4 Theory of Operation ATLAS Series...