25
Save These Instructions
3-90-775R36_09/15
Feed Limit Adjustment
The Circuit board runs on a one minute timer cycle. Each
minute, the board is thinking ahead to what it needs to do
for the next minute to maintain or achieve the demanded
temperature. What you are setting on the Feed Limit dial is
the maximum amount of feed time, per minute, that you'll
allow.
The circuit board will make its own determination of how
long to run the feeder,
UP TO
the maximum, as set on the
dial. For instance, a number 4 setting on the Feed Limit
will allow a maximum of 40 seconds per minute of feed.
If the room temperature is satisfied, with only feeding 20
seconds, then that is all the circuit board will run the feeder.
When heating a large area, the number 4 setting is usually
adequate, however, fuel quality may dictate a higher or
lower setting. If you see unburned or burning fuel being
pushed off of the grate during a high demand period, the
feed rate is set too high. Ideally, you'll want to see about
an inch of ashes in front of the burning fuel during a peak
demand period. When the appliance is located in a smaller
room or area, the Feed Limit may need to be kept at a lower
setting of #2 or #3, to maintain a fire with less frequent shut-
down and ignition cycles. Always allow a minimum of fifteen
minutes between making any adjustments to the feed rate.
Note: Since the circuit board is feeding as needed,
only adjust the feed rate while maximum demand is
occurring. (Constant Burn Mode, with a temp dial
setting of #7 will create maximum demand.)
Mode Selection
Room-Temp mode is the ideal mode of operation if you wish
to maintain a comfortable temperature in the room. As the
outdoor temperature fluctuates, the control will adjust the
feed rate to maintain the desired temperature setting in the
room. For best results, be sure the room sensor is located
away from drafty areas and not positioned on the floor or
near an exterior wall.
Constant Burn mode is more of a manual method of
operation. The stove will run at a constant heat output,
regardless of surrounding air temperature. Note that on the
coldest days, your indoor heated space will be cooler than
on the warmer days. The only real benefit to this mode of
operation is that you'll be able to know exactly how long
a hopper full of fuel will last, because the consumption is
going to stay relatively the same.
Temperature Dial
The temperature dial is a dual purpose dial. In Room-Temp
mode, you select the room temperature you want the stove
to maintain at the room sensor probe. This is marked in
Fahrenheit scale from 50 to 90 degrees. In Constant Burn
mode, you select a temperature setting based on the #1 - 7
with 1 being a minimum burn and 7 being a maximum burn
rate.
Blower Speed Adjustment
The mode selector is also marked with a L to H scale in each
mode. This is a variable speed control for the distribution
blower.
L
is the low setting, and
H
is the high setting. It
is important to note that the blower will not come on until
the ESP reaches a specific temperature, to ensure that cold
air is not being blown out into the room. Also, the speed
of the blower, when set on lower speeds, will automatically
increase as the temperature of the stove increases.
Igniter Auto Mode Switch
The toggle switch for the igniter is a two position switch.
Select from either Igniter Auto or Disabled.
Igniter Auto
- Will automatically start the fire in either
Constant Burn or Room Temp mode.
Constant Burn
: The ignition mode will start the fire one
time only. Since Constant Burn maintains a constant output,
the fire will never go out to need re-ignited.
Room Temp
: The ignition mode will start the first fire. Then,
if the room temperature is satisfied, the fire will go out. Once
the room cools, the ignition mode will start another fire, and
so on. This mode provides fully automatic temperature
control.
Disabled
- The fire must be started manually using starting
gel or other manufactured fire starter.
Disabled
- With the igniter switch in the
MANUAL position,
the igniter is disabled.
Constant Burn
: The fire would need to be started manually,
and will maintain a constant output based on the temperature
setting.
Room Temp
: The fire would need to be started manually.
The control will adjust output to maintain a constant room
temperature, however it will not allow the fire to go out. If
the room temperature is satisfied, the control will adjust
to the minimum burn rate and hold there until the room
temperature decreases.
Содержание P35I
Страница 49: ...49 Save These Instructions 3 90 775R36_09 15 ...