Harman®  •  Accentra52i-TC Installation Manual_R8  •  2017 -___  •  01/19

10

3-90-00584i

Termination Location and Vent Information 

 

A.  Venting Termination Design

#1 Installing into an existing fireplace chimney

This method provides excellent venting with 100% outside air 

which is the most efficient operation of this unit. This method 

also provides natural draft in the event of a power failure. 

A 4” stainless steel flex pipe is needed for the flue pipe, and 3" 

aluminum or Stainless Steel Flex Pipe is used for the intake.

CHIMNEY CONNECTOR PIPE MAY NOT PASS 

THROUGH CONCEALED SPACES INCLUDING AN 

ATTIC, ROOF SPACE, CLOSET, FLOOR OR CEILING.

Height of existing hearth

#2 Installing into an existing fireplace chimney

This method provides excellent venting for normal operation. 

This method also provides natural draft in the event of a 

power failure. 
A cap should be installed on the chimney to keep out rain. 
Combustion air is provided from the living area and enters the 

feed system from around the wing and stove body spaces.

The chimney top must be capped to 

prevent  rain  and/or  snow  from  entering 

the chimney.

See  Figure  4.8,  for  information  on  the 

optional  Harman® Adjustable  Stainless 

Steel Intake Extension.

The damper area must be sealed with a 

steel plate and it is recommended that 

Kaowoll, mineral wool, or an equivalent 

non-combustible  insulation  be  placed 

on top of the sealed area to reduce the 

possibility  of  condensation.  Insulation 

alone should not be used to seal the 

damper opening. For quick and easy 

installation,  purchase  the  steel  Harman 

Block Off Plate, 1-00-25625.

The chimney top must be capped to 

prevent  rain  and/or  snow  from  entering 

the chimney.

The damper area must be sealed with a 

steel plate and it is recommended that 

Kaowoll, mineral wool, or an equivalent 

non-combustible  insulation  be  placed 

on top of the sealed area to reduce the 

possibility  of  condensation.  Insulation 

alone should not be used to seal the 

damper opening. For quick and easy 

installation,  purchase  the  steel  Harman 

Block Off Plate, 1-00-25625.

Figure 4.1

Figure 4.2

DO NOT REMOVE BRICKS OR MORTAR FROM THE 

EXISTING FIREPLACE.

DO NOT REMOVE BRICKS OR MORTAR FROM THE 

EXISTING FIREPLACE.

WARNING

!

WARNING

!

WARNING

!

Содержание Accentra52i-TC

Страница 1: ...rnal part starts to glow you are overfiring Reduce feed rate Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire W...

Страница 2: ...F Combustible Materials Specification 5 G Electrical Codes 5 H California 5 2 Getting Started A Design and Installation Considerations 6 B Tools and Supplies Needed 7 C Inspect Appliance and Component...

Страница 3: ...___________________________ Electrical Section 1 120 VAC unswitched power provided to the appliance ________________________________ Check outlet with multi meter for proper voltage 115 120 VAC ______...

Страница 4: ...D CAUTION DO NOT INSTALL IN SLEEPING ROOM WARNING Weighted average LHV efficiency using data collected during EPA emissions test Weighted average HHV efficiency using data collected during EPA emissio...

Страница 5: ...s any responsibility for and the warranty and agency listing will be voided by the below actions DO NOT Install or operate damaged appliance Modify appliance Install other than as instructed by Hearth...

Страница 6: ...NOT recommended Not the highest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Outside Air Intake on windward side NOT recommended Outside Air Intake on leeward...

Страница 7: ...e glass Read all of the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Hearth Home Technologies disclaim...

Страница 8: ...nsions Use for reference only Figure 3 1 32 1 8 41 13 16 31 5 16 25 9 16 22 20 24 19 9 16 29 15 16 13 16 15 9 16 14 3 8 12 3 4 Unit 1 90 574240 Hopper Capacity 64 5 lbs 29 25 kg Unit 1 90 574220 Hoppe...

Страница 9: ...o Combustibles Floor Protection Floor protection must be used from hearth opening to 6 152mm in front of door glass and 6 152mm to each side of the stove body OR 8 203mm to sides to protect combustibl...

Страница 10: ...ove body spaces The chimney top must be capped to prevent rain and or snow from entering the chimney See Figure 4 8 for information on the optional Harman Adjustable Stainless Steel Intake Extension T...

Страница 11: ...plate and it is recommended that Kaowoll mineral wool or an equivalent non combustible insulation be placed on top of the sealed area to reduce the possibility of condensation Insulation alone should...

Страница 12: ...eal the damper area around the chimney liner with fiberglass batting Note If the Harman Accentra52i TC Pellet Insert is installed into a factory built wood burning fireplace this label Harman part 3 9...

Страница 13: ...throughs and terminations are used Note Flex pipe is not approved these types of installation Detailed installation instructions are included with the Zero Clearance Cabinet These same installation in...

Страница 14: ...ng will require more frequent cleaning It is the responsibility of the installer to make sure the entire flue configuration is accessible for cleaning 4 stainless steel flex vent piping is only allowe...

Страница 15: ...blower every few seconds to clear exhaust until the fire is out Note The UPS provides safe shut down only It is not intended for continued operation Your appliance will recognize when power is restor...

Страница 16: ...st part of the roof This minimizes the effects of wind loading Locate termination cap away from trees adjacent structures uneven roof lines and other obstructions Minimize the use of chimney offsets C...

Страница 17: ...own and Power Failure To reduce the probability of back drafting or burn back in the pellet burning appliance during power failure or shut down conditions the stove must be able to draft naturally wit...

Страница 18: ...sert operates with a positive vent pressure we specify that the joints also be sealed with silicone Where passing through an exterior wall or roof be sure to use the appropriate pass through device pr...

Страница 19: ...each end with an NEC approved grounding device 5 Refer to Clearances to Combustibles and Floor Protection section of this manual for listings to combustibles 6 Use silicone to create an effective vap...

Страница 20: ...during the installation to ensure maximum safety and benefit Inspect appliance and components for damage Damaged parts may impair safe operation Do NOT install damaged components Do NOT install incomp...

Страница 21: ...inge pins See Figure 5 1 2 Remove the ash pan 3 Remove the 4 internal pieces of cast iron Figure 5 2 See Figure 5 3 and Figure 5 4 for removal instructions Figure 5 2 Center Medallion Flame Guide Heat...

Страница 22: ...ifting it upward about 1 2 inch and move the bottom edge front until it sits flat on the firebox bottom 3 Rotate the right side of the heat exchanger toward the door opening until you are able to remo...

Страница 23: ...b assembly base is a round plate which allows it to swivel to allow the flue pipe to exit the mounting frame in other positions rather than straight up Figure 5 10 Figure 5 7 Install 20 x Studs Instal...

Страница 24: ...Connection Installation Note If the room sensor is connected as a return air sensor the wire should be connected long enough to allow this but not too long that it would get tangled or pinched anywhe...

Страница 25: ...he bottom of the top hinge behind the large washer on the center bolt Figure 5 18 Figure 5 18 Slide top hinge behind washer Install the top bolt and washer on the top hinge Finger tighten all 3 bolts...

Страница 26: ...from the control to the rear inside of the body Make sure there are no worn or frayed areas Do not allow pellets or sawdust to build up on the hopper lip Figure 24 Inspect the hopper lid gasket for da...

Страница 27: ...e house CAUTION F Firebox Draft and Combustion Fan RPM These units are pre tested at the factory with exactly 120 VAC 60 Hz They are checked and adjusted for firebox tightness gasket leakage motor ope...

Страница 28: ...USE FIRE USE ONLY APPROVED FUELS AND OPERATION GUIDELINES WARNING THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED CAUTION THE STOVE IS HOT WHILE IN OPERATION...

Страница 29: ...MP 250 VAC 10 AMP YELLOW SKY BLUE BROWN SKY BLUE BLACK 11 LINE FILTER INSIDE BURNPOT IGNITER ELEMENT COMBUSTION MOTOR FEEDER AUGER MOTOR 3 1 2 5 4 8 7 6 SKY BLUE PLUGGED SKY BLUE SKY BLUE BLUE EMPTY Y...

Страница 30: ...___ 01 19 30 3 90 00584i 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer p...

Отзывы: