Installing the Accentra52i-TC Pellet Insert into 

an existing factory built wood burning fireplace

When installing the Accentra52i-TC Pellet Insert into a factory 

built  wood  burning  fireplace,  the  Manufactured  Fireplace 

Installation  Kit  #1-00-574205  must  be  used.  In  addition, 

several things need to be taken into consideration.

The size of the fireplace opening. Will the unit fit into the 

opening?  Many  of  these  units  have  metal  smoke  shields 

inside the top that can be removed to gain height. Often the 

side and rear refractory can be removed to gain depth and 

width. In some circumstances, the front lower lip or grill work 

may also be removed. Be sure and follow the guidelines in 

the kit instructions. Floor protection guidelines, as listed on  

Figure 3.2 must also be followed. 

The factory built chimney must be listed per UL 127 (US) 

and meet type HT requirements of UL 103 (US).  Factory 

Built fireplace chimneys tested to UL 127-98 may be, at the 

fireplace manufacturers option, tested to the same criteria 

as UL 103HT requirements.  If the chimney is not listed as 

meeting HT requirements, or if the factory built fireplace was 

tested prior to 1998, a full height listed chimney liner must be 

installed from the appliance flue collar to the chimney top.  

Liner  must  meet  high  temperature  (2100°  F)  per  UL1777 

(US).  The liner must be securely attached to both the flue 

collar and the chimney cap. To prevent room air passage to 

the chimney cavity of the fireplace, seal the damper area 

around the chimney liner with fiberglass batting.

Note: If the Harman® Accentra52i-TC Pellet Insert is installed into a factory built wood burning fireplace, this label 

(Harman® part #3-90-674204) MUST be attached to the altered fireplace. This label is included in the Manufactured 

fireplace installation kit.

THIS  FIREPLACE  HAS  BEEN  ALTERED  TO  ACCOMMODATE  A 

FIREPLACE INSERT AND SHOULD BE INSPECTED BY A QUALIFIED 

PERSON PRIOR TO REUSE AS A CONVENTIONAL FIREPLACE

Figure 4.5

OPTIONAL HOPPER CONFIGURATIONS FOR SMALLER FIREPLACE 

OPENINGS:

The Harman® Accentra52i-TC Pellet Insert can be factory built with shorter 

hopper configurations.
The standard requires a 24" opening. Part #1-90-584240
Option 1: Requires a 22" opening height. Part #1-90-584220
Option 2: Requires a 20" opening height. Part #1-90-584200

Keep in mind the hopper capacities will decrease with the optional heights.

22"

20"

24"

IN CANADA:

 This  fireplace  insert  must  be  installed  with  a  continuous 

chimney  liner  of  a  minimum  4"  diameter  extending  from  the  insert  to 

the top of the chimney. The chimney liner must conform to the Class 3 

requirements of CAN/ULC-S635, Standard for Lining Systems for Existing 

Masonry  or  Factory  Built  Chimneys  and  Vents,  or  CAN/ULC-S640, 

Standard for Lining Systems for New Masonry Chimneys.

Additionally, the firebox floor of the Zero Clearance Wood or Gas Fireplace may be removed down to the outer metal 

shell of the fireplace if kit 1-00-574305 is used. The kit includes installation instructions and all materials needed to 

remove the firebox floor and still maintain a safe, compliant installation. Be certain to contact local code enforcement 

officials before beginning any modifications, as they may not be reversible in many cases.

Содержание Accentra52i-TC

Страница 1: ...rnal part starts to glow you are overfiring Reduce feed rate Overfiring will void your warranty Comply with all minimum clearances to combustibles as specified Failure to comply may cause house fire W...

Страница 2: ...F Combustible Materials Specification 5 G Electrical Codes 5 H California 5 2 Getting Started A Design and Installation Considerations 6 B Tools and Supplies Needed 7 C Inspect Appliance and Component...

Страница 3: ...___________________________ Electrical Section 1 120 VAC unswitched power provided to the appliance ________________________________ Check outlet with multi meter for proper voltage 115 120 VAC ______...

Страница 4: ...D CAUTION DO NOT INSTALL IN SLEEPING ROOM WARNING Weighted average LHV efficiency using data collected during EPA emissions test Weighted average HHV efficiency using data collected during EPA emissio...

Страница 5: ...s any responsibility for and the warranty and agency listing will be voided by the below actions DO NOT Install or operate damaged appliance Modify appliance Install other than as instructed by Hearth...

Страница 6: ...NOT recommended Not the highest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Outside Air Intake on windward side NOT recommended Outside Air Intake on leeward...

Страница 7: ...e glass Read all of the instructions before starting the installation Follow these instructions carefully during the installation to ensure maximum safety and benefit Hearth Home Technologies disclaim...

Страница 8: ...nsions Use for reference only Figure 3 1 32 1 8 41 13 16 31 5 16 25 9 16 22 20 24 19 9 16 29 15 16 13 16 15 9 16 14 3 8 12 3 4 Unit 1 90 574240 Hopper Capacity 64 5 lbs 29 25 kg Unit 1 90 574220 Hoppe...

Страница 9: ...o Combustibles Floor Protection Floor protection must be used from hearth opening to 6 152mm in front of door glass and 6 152mm to each side of the stove body OR 8 203mm to sides to protect combustibl...

Страница 10: ...ove body spaces The chimney top must be capped to prevent rain and or snow from entering the chimney See Figure 4 8 for information on the optional Harman Adjustable Stainless Steel Intake Extension T...

Страница 11: ...plate and it is recommended that Kaowoll mineral wool or an equivalent non combustible insulation be placed on top of the sealed area to reduce the possibility of condensation Insulation alone should...

Страница 12: ...eal the damper area around the chimney liner with fiberglass batting Note If the Harman Accentra52i TC Pellet Insert is installed into a factory built wood burning fireplace this label Harman part 3 9...

Страница 13: ...throughs and terminations are used Note Flex pipe is not approved these types of installation Detailed installation instructions are included with the Zero Clearance Cabinet These same installation in...

Страница 14: ...ng will require more frequent cleaning It is the responsibility of the installer to make sure the entire flue configuration is accessible for cleaning 4 stainless steel flex vent piping is only allowe...

Страница 15: ...blower every few seconds to clear exhaust until the fire is out Note The UPS provides safe shut down only It is not intended for continued operation Your appliance will recognize when power is restor...

Страница 16: ...st part of the roof This minimizes the effects of wind loading Locate termination cap away from trees adjacent structures uneven roof lines and other obstructions Minimize the use of chimney offsets C...

Страница 17: ...own and Power Failure To reduce the probability of back drafting or burn back in the pellet burning appliance during power failure or shut down conditions the stove must be able to draft naturally wit...

Страница 18: ...sert operates with a positive vent pressure we specify that the joints also be sealed with silicone Where passing through an exterior wall or roof be sure to use the appropriate pass through device pr...

Страница 19: ...each end with an NEC approved grounding device 5 Refer to Clearances to Combustibles and Floor Protection section of this manual for listings to combustibles 6 Use silicone to create an effective vap...

Страница 20: ...during the installation to ensure maximum safety and benefit Inspect appliance and components for damage Damaged parts may impair safe operation Do NOT install damaged components Do NOT install incomp...

Страница 21: ...inge pins See Figure 5 1 2 Remove the ash pan 3 Remove the 4 internal pieces of cast iron Figure 5 2 See Figure 5 3 and Figure 5 4 for removal instructions Figure 5 2 Center Medallion Flame Guide Heat...

Страница 22: ...ifting it upward about 1 2 inch and move the bottom edge front until it sits flat on the firebox bottom 3 Rotate the right side of the heat exchanger toward the door opening until you are able to remo...

Страница 23: ...b assembly base is a round plate which allows it to swivel to allow the flue pipe to exit the mounting frame in other positions rather than straight up Figure 5 10 Figure 5 7 Install 20 x Studs Instal...

Страница 24: ...Connection Installation Note If the room sensor is connected as a return air sensor the wire should be connected long enough to allow this but not too long that it would get tangled or pinched anywhe...

Страница 25: ...he bottom of the top hinge behind the large washer on the center bolt Figure 5 18 Figure 5 18 Slide top hinge behind washer Install the top bolt and washer on the top hinge Finger tighten all 3 bolts...

Страница 26: ...from the control to the rear inside of the body Make sure there are no worn or frayed areas Do not allow pellets or sawdust to build up on the hopper lip Figure 24 Inspect the hopper lid gasket for da...

Страница 27: ...e house CAUTION F Firebox Draft and Combustion Fan RPM These units are pre tested at the factory with exactly 120 VAC 60 Hz They are checked and adjusted for firebox tightness gasket leakage motor ope...

Страница 28: ...USE FIRE USE ONLY APPROVED FUELS AND OPERATION GUIDELINES WARNING THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED CAUTION THE STOVE IS HOT WHILE IN OPERATION...

Страница 29: ...MP 250 VAC 10 AMP YELLOW SKY BLUE BROWN SKY BLUE BLACK 11 LINE FILTER INSIDE BURNPOT IGNITER ELEMENT COMBUSTION MOTOR FEEDER AUGER MOTOR 3 1 2 5 4 8 7 6 SKY BLUE PLUGGED SKY BLUE SKY BLUE BLUE EMPTY Y...

Страница 30: ...___ 01 19 30 3 90 00584i 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer p...

Отзывы: