CLEANING MODE
Triggered by a combination of external input & internal timer or schedule
External Input
Cleaning
Time
Time
Time
Time
Cleaning triggered by Schedule (Calendar)
and External Input
Scheduled Week
Day
Scheduled time
Monday
Tuesday
Wednesday Thursday
Friday
Saturday
Sunday
Start
time1
Start
time2
Start
time3
Start
time1
Start
time2
Start
time3
Cleaning
cycle
Cleaning
cycle
Cleaning
cycle
Cleaning
cycle
Cleaning
cycle
Figure 51:
Cleaning Trigger, External Input & Internal Timer
15.5. STOP CLEANING
Navigation
• Press and hold the keys together to terminate a cleaning.
• During cleaning with the controller in normal measurement mode, the countdown timer will be
displayed on the second LCD line.
A complete rinsing phase (post-rinse time) is always performed before terminating an advance
cleaning. If the request to stop the cleaning is issued during rinsing, the rinsing phase is carried out
to completion.
Note:
Calibration can’t be performed during cleaning; conversely, cleaning can’t be triggered during
calibration.
A cleaning cycle can be stopped:
• At the end of a cleaning sequence, with the next cycle being triggered as per configured cleaning
triggers.
• At a stop command, with the current cycle being shortened to a maximum time which is the sum of
a single rinse and recovery time. Next cycle will start as per configured cleaning triggers.