HAMWORTHY HEATING LTD
60
PUREWELL
Variheat mk2
218612 A03
Individual boilers enabled from B.M.S. using 0-10V analogue input
Legend
E = End user
I = Commissioning F = Heating engineer
Navistem settings
BMS 0-10v Power Control
Menu
Operating Line
User Level Function
Setting
LPB System
6600
F
Device address
1
Configuration 5710
F
Heating
circuit
1
Off
5950
F
Function
input
H1
Output
req
VK1
10v
5951
F
Contact
type
H1
NO
5953
F
Voltage
value
H1
0.1v
5954
F
Function value 1 H1
200 (200 = 20% modulation)
5955
F
Voltage
value
2
H1 10.0v
5956
F
Function valve 2 H1
1000 (1000 = 100% modulation)
5890
F
Relay output QX1
Boiler pump Q1
BMS 0-10v Temperature
Menu
Operating Line
User Level Function
Setting
LPB System
6600
F
Device address
1
Configuration 5710
F
Heating
circuit
1
Off
5950
F
Function
input
H1
Consumer
req
VK1
10v
5951
F
Contact
type
H1
NO
5953
F
Voltage
value
H1
0.5v
5954
F
Function value 1 H1
0 (0 = 0°C)
5955
F
Voltage
value
2
H1 10.0v
5956
F
Function valve 2 H1
800 (800 = 80°C)
5890
F
Relay
output
QX1
Boiler
pump
Q1
Note:
Use H1 wiring connection for 0-10V analog input from B.M.S.
Optional extras required for this configuration:
None
Boiler Parameter Settings: Multiple Boilers
Содержание Purewell Variheat mk2 70c
Страница 30: ...HAMWORTHY HEATING LTD 25 PUREWELL Variheat mk2 218612 A03 Figure 9 0 Boiler Wiring Schematic...
Страница 43: ...HAMWORTHY HEATING LTD 38 PUREWELL Variheat mk2 218612 A03...
Страница 53: ...HAMWORTHY HEATING LTD 48 PUREWELL Variheat mk2 218612 A03 Figure E1 2 Typical Piping Layouts...
Страница 68: ...HAMWORTHY HEATING LTD 63 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 69: ...HAMWORTHY HEATING LTD 64 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 70: ...HAMWORTHY HEATING LTD 65 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 71: ...NOTES...