HAMWORTHY HEATING LTD
27
PUREWELL
Variheat mk2
218612 A03
Loosen captive fittings and remove top and front
covers.
Turn off gas service valve.
Disconnect the gas assembly plug and the low
gas pressure switch plug.
Loosen the gas valve union.
Disconnect the ignitor and flame probe leads.
Carefully remove the power and control cable
from the fan.
Remove the fan / gas valve assembly by
loosening the 4 x M8 nuts securing the transition
duct to the burner.
Loosen the 4 x M8 nuts securing the burner
clamping flange / ring, remove the flange. The
burner can now be carefully lifted off the boiler.
Check the condition of the ignitor and probe
(replace as required).
WARNING: Isolate the electrical supply and turn off the gas isolating valve to the boiler
being serviced.