APPENDIX B - ELECTRICAL CONNECTIONS AND CONTROLS
ELECTRICAL DATA
Model
70c
95c
110c
140c
180c
Normal Supply Voltage
230V ~ 50Hz
Power Consumption (maximum)*
-
W
554
667
Start and Run Current (per boiler)
-
A
0.54
0.6
Figure B1.1 - Electrical Supply
*Where The max allowable power output from the IEC Outlet is 460 W (fitted with A T6.3H fuse).
IMPORTANT: Individual boiler modules must be earthed.
The boiler must be isolated from the mains electricity supply in the event of electric arc
welding being carried out on any connecting pipework.
1.1
Wiring external to the boiler must be installed in accordance with the IET Regulations and any local
regulations which apply. Wiring must be completed in heat resistant 3-core cable of 1.0mm² cross sectional area.
Boilers are normally supplied for connection to a 230 volts, 50Hz mains supply. The Navistem B3000 control is
supplied with a replaceable fuse (T6.3H). External fuses should be 10A for all boiler modules.
1.2
3-Phase Electrical Supplies. Banks of Variheat
mk2 boilers and boilers installed in close proximity to each
other
MUST NOT
be supplied from different phases of a 3 phase supply. The method of connection to the mains
electricity supply must facilitate complete electrical isolation of the single boiler with a separation of at least 3mm
in all poles.
1.3
A mains isolator must be provided adjacent to each boiler in a readily accessible position. The supply should
only serve the boiler.
1.4
Volt free contact electrical supplies must be isolatable where fitted.
1.5
Further details regarding connection to the electricity supply are given in BS EN 60335, Part 1.
WARNING: THE MAINS POWER SUPPLY MUST NOT BE SWITCHED
BY A TIME-CLOCK CONTROL
CAUTION: DO NOT FEED MAINS VOLTAGE ONTO THE TIMER TERMINALS
1.6
The mains power supply must be maintained at all times. Each Purewell Variheat
mk2 boiler incorporates a
remote stop/start loop, which can be used to operate the boiler(s) under a timed regime. The boiler controls
provide a 5V DC signal that can be fed through a volt free contact for operation. Refer to BS 6644 for further
information on installing the electrical supply.
NOTE:
FOR ELECTRICAL CONNECTIONS TO BOILER SEE FIGURE 4.6
FOR BOILER WIRING SCHEMATIC SEE FIGURE 9.0
FOR MULTIPLE BOILER WIRING SEE FIGURE B1.2 & B1.3
FOR CONTROL WIRING SEE FIGURE E1.3.1 TO E1.3.4
Содержание Purewell Variheat mk2 70c
Страница 30: ...HAMWORTHY HEATING LTD 25 PUREWELL Variheat mk2 218612 A03 Figure 9 0 Boiler Wiring Schematic...
Страница 43: ...HAMWORTHY HEATING LTD 38 PUREWELL Variheat mk2 218612 A03...
Страница 53: ...HAMWORTHY HEATING LTD 48 PUREWELL Variheat mk2 218612 A03 Figure E1 2 Typical Piping Layouts...
Страница 68: ...HAMWORTHY HEATING LTD 63 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 69: ...HAMWORTHY HEATING LTD 64 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 70: ...HAMWORTHY HEATING LTD 65 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 71: ...NOTES...