HAMWORTHY HEATING LTD
19
PUREWELL
Variheat mk2
218612 A03
High Fire Target
Nat Gas 9.5% ±0.25% CO
2
If combustion level is outside of this range use an
allen key to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.4.5.1a - Adjusting gas valve throttle
180c
Low Fire Target 95c & 110c -
Nat Gas 9.5% ±0.25% CO
2
140c -
Nat Gas 8.5% ±0.25% CO
2
If combustion readings are outside target range use a
cross-slot screwdriver to make adjustments.
To increase the CO
2
level, turn the adjustment clock-
wise.
Figure 7.4.4.1b —Adjusting gas valve offset
Low Fire Target
Nat Gas 8.5% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 7.4.5.1b —Adjusting gas valve offset
95c/110c/140c
180c
High Fire Target
Nat Gas - 9.5% ±0.25% CO
2
If combustion level is outside of this range use a
slotted screwdriver to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.4.4.1a - Adjusting gas valve throttle
95c/110c/140c
Содержание Purewell Variheat mk2 70c
Страница 30: ...HAMWORTHY HEATING LTD 25 PUREWELL Variheat mk2 218612 A03 Figure 9 0 Boiler Wiring Schematic...
Страница 43: ...HAMWORTHY HEATING LTD 38 PUREWELL Variheat mk2 218612 A03...
Страница 53: ...HAMWORTHY HEATING LTD 48 PUREWELL Variheat mk2 218612 A03 Figure E1 2 Typical Piping Layouts...
Страница 68: ...HAMWORTHY HEATING LTD 63 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 69: ...HAMWORTHY HEATING LTD 64 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 70: ...HAMWORTHY HEATING LTD 65 PUREWELL Variheat mk2 218612 A03 NOTES...
Страница 71: ...NOTES...