HAMWORTHY HEATING LTD 

 

PUREWELL

 

Variheat mk2 

 

218612 A03 

 

1.0 INTRODUCTION 

 

 

1.1

 

A competent person holding ‘GAS SAFE’ 

registration or equivalent must install this boiler.  All 
installations 

MUST

 conform to the relevant Gas 

Safety and Building Regulations. Health & Safety 
requirements must also be taken into account when 
installing any equipment. Failure to comply with the 
above may lead to prosecution. 
 
This appliance is not intended for use by persons 
(including children) with reduced physical, sensory or 
mental capabilities, or lack of experience and 
knowledge, unless they have been given supervision 
or instructions concerning cleaning, maintenance and 
use of the appliance by a person responsible for their 
safety. Children should be supervised to ensure that 
they do not play with the appliance.  
 

1.2

 These instructions are for Group H Natural Gas 

(2nd Family) only. The information relating to Natural 
Gas firing is to be found in Appendix ‘A’. Boilers 

MUST 

NOT

 use gas other than that for which they were 

designed and made. 
 

1.3

 The Purewell Variheat mk2 is a fully modulating, 

pre-mix condensing, gas fired boiler manufactured 
from horizontal cast iron heat exchanger sections, 
connected to an economiser located in the base of 
the boiler. The boiler is floor mounted and is intended 
for the heating of Commercial and Industrial 
premises. It may also be used to supply hot water for 
these premises via an indirect cylinder. 
 

1.3.1 

Operation is initiated and controlled by a Navistem 

boiler management system with a user interface LCD 
display for accessing and changing boiler parameters. 

 
1.3.2 

The Purewell Variheat mk2

 

boiler is delivered to 

site fully assembled  fitted with it’s casing and 
controls. Care should be taken when manoeuvring 
the boiler into position to avoid damage. 

 
1.3.3  

Each of the boiler models is designed for direct 

connection to a flue system. The flue system must be 
suitable for pressurised wet operation. The flue 
outlets from more than one unit may be connected to 
a single chimney. No draught diverter is fitted to the 
boiler nor is a fixed diverter required in the flue 
system. However a draught stabiliser is 
recommended for some installations —see Appendix 
‘C’ (Page 41). 
 

1.3.4  

The Purewell Variheat

 

mk2

 

has a low water 

content and minimum flow rates 

MUST

 be maintained 

above the recommended levels shown in Appendix 
‘E’ (Page 45).

 

 

1.4

 If the boiler is to be connected to an un-vented 

(pressurised) heating system, care must be taken to 
ensure all extra safety requirements are met and that 
the relevant interlocks will shut down the boiler(s) 
should a high or low pressure fault occur.

 

 

 

The pressurisation unit must also incorporate a low 
level water switch, which protects the water pumps, 
and will directly or indirectly shut down the boiler 
plant should a low water condition occur

.   

 

Consideration should also be given to the maximum 
working pressure of the boiler as per Appendix ‘E’. 
Consult Hamworthy Heating Technical Department 
for help or assistance if in doubt. 
 

1.5

 The Purewell Variheat mk2

 

boiler is not suitable 

for direct connection to domestic hot water supplies 
or gravity fed heating systems.

 

 

1.6

 The Purewell Variheat mk2 boiler can be installed 

with either reverse return water flow layout  or with 
single pipe header layout (non HHL supply). See  
Appendix E for typical schematic layout.

 

 

1.7

 It is good practice in all heating installations to 

use some form of water treatment to reduce 
formation of lime scale and black iron oxide sludge. 
The high efficiencies produced by the Purewell 
Variheat

 

mk2

 

Boiler can easily be reduced by lime 

scale formation. If a pressurisation unit is used, it is 
prudent to include an hours run meter to give an 
indication of pump running time and hence raw water 
make-up. Any leaks should be attended to as soon as 
possible to avoid scale build up within the boiler's 
waterways. 

 

1.8  

Each Purewell Variheat

 

mk2 module is supplied 

with volt free contact outputs for  Normal Run, Boiler  
lock-out from a General Fault, 0~10v analogue 
control input. Also provided are connections for BMS, 
Shunt Pump & Remote On/Off control as well as 
connections to a boiler lock circuit (causing the boiler 
to go to standby). 
 

1.9 Options 
1.9.1 

Optional reverse return header kits are 

available in 2, 3 & 4 boiler configuration covering 
models 70c, 95c, 110c, 140c & 180c. These kits 
incorporate all necessary valves and interconnecting 
pipework. Refer to individual kit instructions for 
details.

 

 

1.9.2  

Controls peripherals  

The Navistem boiler management system has the 
potential to accept the following control options: 

 

1.9.3 

OCI345 LPB Clipin – Kit part number: 563605667 

BSB to LPB interface to allow communication between 
boilers for Cascade of 16 boilers by LMS or 
communication to external RVS system components 
(e.g. Merley sequence controller).  

 

1.9.4  

For additional kit information please refer to 

Appendix F (page 50).  
 
 
 
 
 
 

 

Содержание Purewell Variheat mk2 70c

Страница 1: ...tic Ignition for Heating and Domestic Hot Water Installations Installation Commissioning and Servicing Instructions MODELS 70c 95c 110c 140c 180c NATURAL GAS I2H IMPORTANT NOTE THESE INSTRUCTIONS MUST...

Страница 2: ...by our own engineers accredited agents or specialist sub contractors will ensure the equipment is operating safely and efficiently Service Contracts Regular routine servicing of equipment by Hamworth...

Страница 3: ...2ND FAMILY I2H PLEASE ENSURE RELEVANT INFORMATION REQUIRED WITHIN DOCUMENT IS FOUND BEFORE FIRING BOILER COUNTRY OF DESTINATION UNITED KINGDOM REPUBLIC OF IRELAND THIS BOILER COMPLIES WITH ALL RELEVA...

Страница 4: ...6 0 PRE COMMISSIONING 13 6 1 Gas Supply 6 2 Ventilation 6 3 Pipework Valves and Pump 6 4 Flue 6 5 Electrical 7 0 CHECKS PRIOR TO LIGHTING 14 7 1 Boiler Gas System Leak Check 7 2 Checks Prior to Light...

Страница 5: ...EWELL Variheat mk2 218612 A03 3 iii PAGE APPENDICES APPENDIX A GAS DATA 38 APPENDIX B ELECTRICAL CONNECTIONS AND CONTROLS 39 APPENDIX C FLUE DATA 41 APPENDIX D VENTILATION 44 APPENDIX E WATER DATA 45...

Страница 6: ...hown in Appendix E Page 45 1 4 If the boiler is to be connected to an un vented pressurised heating system care must be taken to ensure all extra safety requirements are met and that the relevant inte...

Страница 7: ...ns relating to the lifting of heavy loads Protect the boiler against slippage by means of a transport strap NOTICE Boiler damage through impact The standard delivery of the boiler includes components...

Страница 8: ...ase provide details of your order such as order number and contract number as well as a detailed description of the missing item Reverse Return Header Sets Where reverse return header sets are used th...

Страница 9: ...llowance for sufficient access at front sides and rear of boiler for flue and pipework connections Ensure a minimum height of 150mm above the boiler for removal of the covers Do not run cabling throug...

Страница 10: ...iler installation Safety Valve As each kit is provided with a 3 port isolating valve for use on the flow pipe individual safety valves are not required on each module and a common valve can be fitted...

Страница 11: ...on of boilers manifold kits pipework pumps controls flues ventilation access and servicing and other items of plant 4 2 Gas Supply Gas supply pipes must be in accordance with BS 6891 or IGE UP 2 Gas s...

Страница 12: ...must be designed to limit the max suction cold to 30Pa negative measured at the connection to the boiler If the suction is greater than 30Pa refer to HHL Technical This condition must then be checked...

Страница 13: ...HAMWORTHY HEATING LTD 8 PUREWELL Variheat mk2 218612 A03 Figure 4 3 Flue Connection Point Flue Connection as delivered Flue Connection fitted Flue fixing bracket Flue Pipe Elbow...

Страница 14: ...e system pipework is flushed twice before water treatment In hard water areas 180mg CaCO3 litre precautions such as water treatment are strongly recommended to prevent the build up of sludge and scale...

Страница 15: ...d not copper Hamworthy recommend 32mm dia Plastic waste pipe Condense may be discharged to a standard drain subject to National or Local regulations Boiler Condensate Connection 32mm o d Figure 4 5 1...

Страница 16: ...n Electrical isolators must have contact separation of minimum 3mm in all poles Electrical isolators must be installed in readily accessible locations Electrical supplies to boiler modules should only...

Страница 17: ...put Remote On Off 0 10v Analogue Control Signal Input Outside Temperature sensor LPB Bus Connection Option 5 0 BOILER ASSEMBLY General Boilers are despatched to site as fully assembled units The flue...

Страница 18: ...tilation and air supply to plantroom is correct refer to Appendix D page 44 Air supply around the rear of appliance is unobstructed 6 3 Pipework Valves and Pump Ensure that Pipework and valve arrangem...

Страница 19: ...the electrical power and gas to the appliance 2 By unscrewing screw at Position X of Figure 7 1 1 remove the red gas pressure switch L H S picture or loosen the test point valve plug R H S picture 3...

Страница 20: ...s hole in the controls fascia using a terminal screwdriver If satisfactory refit the bulb in the pocket and secure with the clip Ensure that all limiter bulbs sensors are fully inserted into the pocke...

Страница 21: ...e Navistem manual HHL part no 500001310 3 As the gas valve is closed the low gas pressure switch will prevent the boiler from firing and the error code E132 will be displayed on the screen Refer to se...

Страница 22: ...flame probe The boiler will shutdown attempt to relight once then lock out causing Error code E133 to appear on the display Carefully reconnect the probe lead then press the Reset button to recommence...

Страница 23: ...7 If the combustion readings fall within the required range the boiler is set and operating correctly 8 Remove the combustion analyser probe replace the sample point plug in the front of the base of t...

Страница 24: ...slot screwdriver to make adjustments To increase the CO2 level turn the adjustment clock wise Figure 7 4 4 1b Adjusting gas valve offset Low Fire Target Nat Gas 8 5 0 25 CO2 If combustion readings are...

Страница 25: ...ustment Factory Sealed Pressure Feed Back Tube Outlet Gas Pressure Test Point Pressure Switch Pressure Switch High Fire Gas Adjustment Factory Sealed Low Fire Gas Adjustment Factory Sealed Outlet Gas...

Страница 26: ...n should be given describing each functional step This Installer s Guide and User s In structions should then be handed over kept in a safe place for easy reference Figure 7 7 1 Burner pressure test p...

Страница 27: ...de HHL part no 500001309 is supplied with each boiler This guide gives instruction on initial set up as well as a list of possible error codes The Navistem controller is located on the main control pa...

Страница 28: ...setpoint Holiday function active Heating to the Reduced set point Reference to heating circuit Heating to the frost protection setpoint Service special functions Cooling to cooling setpoint Error mes...

Страница 29: ...must be used to maintain the internal building temperature 8 3 2 Pump overrun When the heating mode ends the heating circuit pump remains on for a period depending on the settings used QAA74 544 In d...

Страница 30: ...HAMWORTHY HEATING LTD 25 PUREWELL Variheat mk2 218612 A03 Figure 9 0 Boiler Wiring Schematic...

Страница 31: ...ontroller monitors the flame s ability to rectify an AC current If the flame diminishes for whatever reason and the rectified current drops below the controller s minimum detection current the control...

Страница 32: ...leads Carefully remove the power and control cable from the fan Remove the fan gas valve assembly by loosening the 4 x M8 nuts securing the transition duct to the burner Loosen the 4 x M8 nuts securi...

Страница 33: ...non return valve Inspection of the fan impellor can normally be checked at this point Heat exchangers do not normally require cleaning but if deposits have accumulated compressed air or water can be u...

Страница 34: ...gas soundness after replacement parts have been fitted Refer to Section 7 1 if necessary for valve integrity check procedure 4 Re light the boiler using instructions on the inside of the door Check f...

Страница 35: ...1 Ignition Electrode and Flame Sensing Probe Positions Figure 11 2 1 Gas Valve Assembly Models PV70c 208 Venturi Seal 207 Venturi 205 Gas Pressure Switch 206 Gas Valve 220 View Port Glass 219 Ignitor...

Страница 36: ...A03 Figure 11 2 2 Combustion System Assembly Model PV70c 207 Gas Air Mixer Venturi 206 Gas Valve 209 Fan 205 Gas Pressure Switch Figure 11 3 1 Gas Valve Assembly Models PV95c 110c 140c 208 Venturi Se...

Страница 37: ...on System Assembly Model PV95c 110c 140c 207 Gas Air Mixer Venturi 206 Gas Valve 209 Fan 205 Gas Pressure Switch Figure 11 3 3 Combustion System Assembly PV70c 95c 110c 140c 201 Burner 212 Flapper Val...

Страница 38: ...y PV180c 209 Fan 205 Gas Pressure Switch 206 Gas Valve 214 Gas Valve Mounting Bracket 207 Gas Air Mixer Venturi Figure 11 4 2 Combustion System Assembly Model PV180c 209 Fan 205 Gas Pressure Switch 20...

Страница 39: ...ontrol Cover Assembly 510 Screw 510 Screw 510 Screw Figure 11 6 Casing Assembly 216 Gas Pipe 217 1 Ball Valve Gas Test Point 214 Gas Hose Figure 11 5 Gas Train Assembly 510 Retaining Washer 503 Top Co...

Страница 40: ...istribution Screen 53242001 Secondary Heat Exchanger 512 Secondary Heat Exchanger Gasket 511 Base Top 408 Section Clamp 411 Thermostat Pocket 406 Burner Gasket 403 Combustion Chamber 405 Heat Exchange...

Страница 41: ...hanger Assembly model 140c 180c shown for illustration 407 Tie Rod 404 Heat Exchanger No Fins 410 Tube 410 O Ring 410 Elbow 410 O ring 409 3 Section Flexible Connector 405 Heat Exchanger Fins 403 Comb...

Страница 42: ...in this manual Please Note To ensure the correct spare parts are despatched by our spares department it is imperative that the complete Boiler Module Control Panel Serial Numbers are given The Boiler...

Страница 43: ...HAMWORTHY HEATING LTD 38 PUREWELL Variheat mk2 218612 A03...

Страница 44: ...ow Gasket 211 Ignitor Top Gasket 218 Ignitor Face Gasket 219 Gas Valve 206 Gas Valve O Ring 213 Gas Hose 215 Combustion Fan 209 Combustion Fan Seal 210 Low Gas Pressure Switch 205 Set of Gaskets Routi...

Страница 45: ...egulations Seasonal Efficiency gross 95 3 95 6 95 8 95 7 94 6 Natural Gas GAS DATA Gas Inlet Connection Pipe Thread Size R1 Nominal Gas Inlet Pressure mbar 20 Maximum Gas Inlet Pressure mbar 25 Gas Fl...

Страница 46: ...in close proximity to each other MUST NOT be supplied from different phases of a 3 phase supply The method of connection to the mains electricity supply must facilitate complete electrical isolation o...

Страница 47: ...HAMWORTHY HEATING LTD 42 PUREWELL Variheat mk2 218612 A03 Figure B1 2 External Control Wiring for Multiple Module Installation 15...

Страница 48: ...tallations b Care should be taken to ensure that the flue is installed such that any condensation is continuously drained All flues should have a maximum slope of 2 upwards in the direction of the exh...

Страница 49: ...erminal or grille to stop ingress of birds etc C1 7 Surface Temperatures Combustible materials in the vicinity of the boiler and flue shall not exceed 65 C during boiler operation The flue shall not b...

Страница 50: ...5c 110c 140c 180c Straight tube 150mm maximum length m 131 114 114 79 57 45 bend 150mm Equivalent tube length m 1 6 1 7 1 7 1 8 1 8 90 bend 150mm Equivalent tube length m 2 1 2 2 2 2 2 3 2 3 Model Fig...

Страница 51: ...shall be such that the maximum temperatures within the boiler house shall be as follows 1 At floor level or 100mm above floor level 25 C 2 At mid level 1 5m above floor level 32 C 3 At ceiling level o...

Страница 52: ...tem including the boiler and hot water storage vessel 4 Each boiler module has R2 male flow indicated with a red spot and return indicated with a blue spot connections Boilers should be connected by f...

Страница 53: ...HAMWORTHY HEATING LTD 48 PUREWELL Variheat mk2 218612 A03 Figure E1 2 Typical Piping Layouts...

Страница 54: ...e that the minimum flow rate can be obtained It is also important that the existing system be flushed through twice to remove any loose matter which may have accumulated If in any doubt regarding the...

Страница 55: ...ion vessel required Care must be taken in sizing expansion vessels to ensure maximum acceptance factors are not exceeded Normally manufacturers of vessels impose a limit of 0 5 This value must not be...

Страница 56: ...2 218612 A03 Figure E 1 3 4 Schematic for Multiple Boiler Cascade Primary Circuit System Figure E 1 3 3 Schematic for Single Boiler External 0 10V Multi Circuit System MERLEY CONTROLLER MERLEY Optiona...

Страница 57: ...linder sensor kit QAZ36 563605674 Heating circuit sensor kit QAZ36 563605673 Strap On Water temperature sensor kit QAD36 533901594 Offset Room sensor QAA55 563605696 Programmable Room sensor 563605695...

Страница 58: ...HAMWORTHY HEATING LTD 53 PUREWELL Variheat mk2 218612 A03 Hydraulic Schemes 1 2 These schematics are available to download at www hamworthy heating com...

Страница 59: ...HAMWORTHY HEATING LTD 54 PUREWELL Variheat mk2 218612 A03 Hydraulic Schemes 3 4 These schematics are available to download at www hamworthy heating com...

Страница 60: ...HAMWORTHY HEATING LTD 55 PUREWELL Variheat mk2 218612 A03 Hydraulic Schemes 5 6 These schematics are available to download at www hamworthy heating com...

Страница 61: ...HAMWORTHY HEATING LTD 56 PUREWELL Variheat mk2 218612 A03 Hydraulic Schemes 7 8 These schematics are available to download at www hamworthy heating com...

Страница 62: ...h respect to their parameter setting as heating cir cuits 1 2 have pre defined outputs for each extension module as shown in the table below Boiler Parameter Settings Single Boiler Note To check opera...

Страница 63: ...ompensation Legend E End user I Commissioning F Heating engineer Menu Operating Line User Level Function Setting LPB System 6600 F Device address 1 6630 F Cascade Master Automatically Heating Circuit...

Страница 64: ...pump Q25 5931 F Sensor input BX2 Boiler 1 Master Common flow sensor B10 Boilers additional set to none 6117 F Central compensation set up Boilers all set to 5 6200 F Save sensors Boilers all set to y...

Страница 65: ...lation 5955 F Voltage value 2 H1 10 0v 5956 F Function valve 2 H1 1000 1000 100 modulation 5890 F Relay output QX1 Boiler pump Q1 BMS 0 10v Temperature Menu Operating Line User Level Function Setting...

Страница 66: ...5 ect 6601 F Segment address Boilers all set to 0 6640 F Clock mode Boilers all set to Slave with remote setting Configuration 5710 F Heating Circuit 1 Boilers all set to off 6200 F Save sensors Boile...

Страница 67: ...HAMWORTHY HEATING LTD 62 PUREWELL Variheat mk2 218612 A03 INSTALLER SITE ADDRESS BOILER TYPE BOILER SIZE S UNIT NO S SERIAL NO S FLUE USEFUL USER INFORMATION NOTES...

Страница 68: ...HAMWORTHY HEATING LTD 63 PUREWELL Variheat mk2 218612 A03 NOTES...

Страница 69: ...HAMWORTHY HEATING LTD 64 PUREWELL Variheat mk2 218612 A03 NOTES...

Страница 70: ...HAMWORTHY HEATING LTD 65 PUREWELL Variheat mk2 218612 A03 NOTES...

Страница 71: ...NOTES...

Страница 72: ...lfast BT3 9JP Tel 028 9077 7737 Email hvacsupplies btconnect com Scotland Sales Service McDowall Modular Services 2 Penson Road Queenslie Industrial Estate Glasgow G33 4AG Tel 0141 336 8795 fax 0141 3...

Отзывы: