Hampton® H35-10 Direct Vent Freestanding Gas Stove

 | 

14

installation

INSTALLATION  
PRECAUTIONS

These venting systems are engineered products that 

have been designed and tested for use with the H35-

NG10, and H35-LP10. The warranty will be voided 

and serious fire, health or other safety hazards may 

result from any of the following actions:

1)

  Installation of any damaged Direct Vent compo-

nent

2)

  Unauthorized  modification  of  the  Direct  Vent 

System

3)

  Installation of any component part not 

      approved by FPI - Fireplace Products 

      International Ltd.

4)

  Installation other than as instructed by the ap-

proved rigid pipe manufacturers and FPI Fireplace 

Products International Ltd.

Warning:    Always  maintain  required 

clearances (air spaces) to nearby com

-

bustibles to prevent a fire hazard. Do 

not fill air spaces with insulation. 

Be  sure  to  check  the  vent  termination  clearance 

requirements  from  decks,  windows,  soffits,  gas 

regulators, air supply inlets and public walkways as 

specified in the "Exterior Vent Terminal Locations" 

section and in your local building codes.

The  gas  appliance  and  vent  system  must  be 

vented  directly  to  the  outside  of  the  building, 

and never be attached to a chimney serving a 

separate solid fuel or gas-burning appliance.

 Each 

direct vent gas appliance must use it's own separate 

vent system. Common vent systems are prohibited.

SAFETY PRECAUTIONS FOR 
THE INSTALLER

1)

  Wear gloves and safety glasses for protection.

2)

  Exercise extreme caution when using ladders or 

on roof tops.

3)

  Be aware of electrical wiring locations in walls 

and ceilings.

Note: These flue pipes must not be 

connected to any other appliance.

The gas appliance and vent system must be vented 

directly to the outside of the building, and never 

be attached to a chimney serving a separate solid 

fuel or gas burning appliance. Each direct vent gas 

appliance must use it's own separate vent system. 

Common vent systems are prohibited.

 IMPORTANT

Read all instructions carefully before starting the 

installation. Failure to follow these instructions may 

create a fire or other safety hazard, and will void the 

warranty. Be sure to check the venting and clear-

ance to combustible requirements.   Consult your 

local building codes before beginning installation.

The location of the termination cap must conform 

to the requirements in the "Exterior Vent Terminal 

Locations" section.

VENT RESTRICTOR  
POSITION

Vent restriction is required for certain venting instal-

lations, see the diagrams in "Venting Arrangement" 

section to determine if they are required for your 

installation. 

To set the Vent restriction as indicated in the dia-

grams in the "Venting Arrangement" section,  simply 

loosen the screws and push the vent restrictor plate 

to the correct position. Tighten the screws.

Horizontal Termination: Position "A"

Vertical Termination: Position "B"

VENTING  
INTRODUCTION

The Horizontal Termination Kit and the rigid pipe 

venting systems, in combination with the  Direct 

Vent Freestanding Gas Stoves, H35-NG10 and 

H35-LP10, have been tested and listed as direct 

vent heater systems by Warnock Hersey. 

These units use the "balanced  flue"  technology 

Co-Axial system. The inner liner vents products 

of combustion to the outside while the outer pipe 

draws outside combustion air into the combus-

tion chamber thereby eliminating the need to use 

heated room air for combustion and losing warm 

room air up the chimney.

Содержание H35-10

Страница 1: ...AT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave the building immediately Immediately call your gas supplier f...

Страница 2: ...has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch The model H35 10 has been approved by Warnock Hersey Intertek for both safety and efficiency...

Страница 3: ...7 7 6 5 1 6 7 3523 57 2 3 7 7 0 127 23 1 2 25 1 3 57 25 6 26 72 7 5 3 57 7 287 285 35 25 5 77 1 216 17 855 17 5 9 6 21 35 9 286 5 9 6 21 3 57 0 7 1 8 5 16 1 5 81 76 1 1 6 0 16 216 72 5 1 6 81 66 27 5...

Страница 4: ...2 25 1 3 57 25 6 26 72 7 5 3 57 7 287 285 35 25 5 77 1 216 17 855 17 5 9 6 21 35 9 286 5 9 6 21 3 57 0 7 1 8 5 16 1 5 81 76 1 1 6 0 16 216 72 5 1 6 81 66 27 5 6 67 7 6 2 127 352 7 21 5 1 02 47 5 9 3...

Страница 5: ...rangements 20 Vertical Termination With Co linear Flex System 23 DV Stove Horizontal Termination Vent Kit 24 Dura Vent Termination Kit 26 Horizontal Installations 27 Rigid Vent system 27 Vertical Term...

Страница 6: ...25 1 NFPA 501A Manufactured Home Installations Standard or ANSI A119 2 ou NFPA 501C Standard for Recreational Vehicles This appliance is only for use with the type of gas indicated on the rating plate...

Страница 7: ...directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT...

Страница 8: ...isapplianceisonlyforusewiththetype of gas indicated on the rating plate This appliance is not convertible for use with othergases unlessacertifiedkitisused BEFORE YOU START Safe installation and opera...

Страница 9: ...h the operation to use the fireplace INSTALLATION CHECKLIST 1 Locate your appliance Refer to the following sections a Clearances to combustibles b Locating Your Gas Stove c For venting requirements se...

Страница 10: ...f unit LOCATING YOUR GAS STOVE When selecting a location for your stove ensure that the clearances listed above are met as well as ensuring that there is adequate accessibility for servicing and prope...

Страница 11: ...lve cover plate to the base panel through the large grommet 8 Attach the connectors black and red of Fan Grey wire to the IFC connectors black and red NOTE Do remember to follow the wire color code i...

Страница 12: ...ver 3 Remove upper panel 4 Remove all the 4 screws that secure elbow to unit using a 1 4 magnetic nut driver 5 Rotate elbow 180O 6 Secure the elbow with 4 screws 7 Reverse steps 6 1 to reinstall the u...

Страница 13: ...11mm socket 3 Remove top cast grill by pulling it up 5 Loosen front casting mounting bolts using a 7 16 or 11 mm socket 6 Open the valve aceess door and loossen the bottom front casting bolts using th...

Страница 14: ...e flue pipes must not be connected to any other appliance Thegasapplianceandventsystemmustbevented directly to the outside of the building and never be attached to a chimney serving a separate solid f...

Страница 15: ...of center line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air...

Страница 16: ...ble Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 0...

Страница 17: ...tion 14 46DVA VCH N A N A N A N A TM 4ST14 Snorkel Termination 36 46DVA HC N A N A N A N A TM 4ST36 Basic Horizontal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit...

Страница 18: ...mp AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direct Vent Pro are registered and or proprietary trademarks of Simpson Dura Vent Co Inc This product...

Страница 19: ...Homes after first sale Horizontal Terminations for All Venting Systems The shaded areas in the diagram below show allallowablecombinationsofverticalrunswith horizontal terminations Maximum one 90O elb...

Страница 20: ...permitted Venting Arrangements Straight Horizontal Termination The diagrams show all allowable combina tionsofstraighthorizontalterminationusing Rigid Pipe Restrictor position A Only a snorkel or FPI...

Страница 21: ...ith min of 9 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required With these options maxi mum total pipe length is 30 feet with minimum of 8 feet t...

Страница 22: ...te min 1 foot between 90o elbows is required Option H H1 V A 2 Max 2 Min B 3 Max 3 Min C 4 Max 4 Min D 5 Max 5 Min E 6 Max 6 Min Withtheseoptions max total pipelengthis30feetwithmin of6feettotalvertic...

Страница 23: ...3 76mm co linear aluminium flex running the full length of the chimney See the Venting Arrangements chart below for minimum and maximum flue lengths See chart below for minimumdistancesfromroof Perio...

Страница 24: ...if the centerline cannot be met the adjustable sections will have to be cut e Cut the 4 ft section of rigid pipe to length Attach the 45o elbow to the rigid pipe and ensure that the pipe length when c...

Страница 25: ...e desired size Hint leave an extra 12 to 16 of length this will make the final assembly easier to work with 9 Securethe4 dia flexlinertothe4 adaptorwith Mill Pac and 3 of the 8 x 1 2 screws stainless...

Страница 26: ...the unit to the wall It is also important to note the wall thickness The wall thimble is suitable for 2 x 4 or 2 x 6 wall construc tion Select the amount of vertical rise desired for vertical to horiz...

Страница 27: ...adaptor is installed on the unit at the factory Assemble the desired combination of pipe and elbows to the ap pliance adaptor with pipe seams oriented towards the wall or ceiling as much out of view...

Страница 28: ...4inches Securetheconnection between the vent pipe and the vent cap by attaching the two sheet metal strips extend ing from the vent cap assembly into the outer wall of the vent pipe Use the two sheet...

Страница 29: ...ction Failure to do so may result in drafting or performance issues not covered under warranty 4 Assemblethedesiredlengthsofblackpipeand elbows necessary to reach from the appliance adaptor up though...

Страница 30: ...cleanout doors and caps or plugs for cleanout tee fittings and ash dumps shall be secured in place and sealed before installing a Direct Vent system within the chimney If the appliance shuts off duri...

Страница 31: ...FOR LEAK TESTING CATHEDRAL CEILINGS Round Support RDS Square Support SQS If your home has a cathedral ceiling no attic space betweentheceilingandtheroof installthechimney and support as follows 1 Situ...

Страница 32: ...When finished reading manometer turn off the unit disconnect the hose and tighten the screw clockwise with a 1 8 flat screwdriver Note Screw should be snug but not over tightened Caution Carbon will...

Страница 33: ...t cap to expose the pilot orifice 6 Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit and replace pilot cap 7 Remove burner orifice with a 1 2 wrench and di...

Страница 34: ...l first by carefully slipping it between the back wall of the firebox and the rear log bracket Back Panel Diagram 1 4 Before installing the side brick panels loosen thescrewsforthebricktabsenoughsotha...

Страница 35: ...02 48 C 02 44 B 02 56 F 02 47 E 02 45 Embers Embers C 02 44 Pins on Rear Log Support A 02 43 B 02 56 4 Place Rear Log A 02 43 on the two pins on the rear log support 5 Place the Middle Left Log B 02...

Страница 36: ...ULC or UL approved may be used CAUTION Do not connect the millivolt wall thermostat wires to the 120V wires Recommended Maximum Lead Length Two Wire When Using Wall Thermostat CP 10 System Wire Size M...

Страница 37: ...ve the grounding prong from this plug Note 4 AA Batteries must be installed into the back up battery compartment however for this unit to operate when power is lost See battery back up instructions in...

Страница 38: ...X8 X9 X6 11 5 X7 SW1 1 5V AA type 1 5V AA type 1 5V AA type 1 5V AA type RED YELLOW YELLOW BLACK BLACK GREEN VARIABLE LIGHT MAIN LINE SPARK FLAME DETECT RED BLACK BATTERY PACK MAIN ON OFF SWITCH YELLO...

Страница 39: ...hile it is hot OPERATING INSTRUCTIONS 1 Read and understand these instructions before operating this appliance 2 Check to see that all wiring is correct and en closed to prevent possible shock 3 Check...

Страница 40: ...tely 60 seconds If there is still no positive ignition the board will go into lock out The system will need to be reset as follows a Wait 5 minutes turn the system off by pressing the ON OFF button on...

Страница 41: ...nsult a qualified installer service agency or gas supplier AVERTISSEMENT Quiconque ne respecte pas la lettre les instructions dans la pr sente notice risquede d clencher un incendie ou une explosion e...

Страница 42: ...and and contract at different rates resulting in some cracking and ticking sounds will be heard throughout the cycling process WARNING CHILDRENANDADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFAC...

Страница 43: ...MENT Theunitshouldneverbeusedwithbrokenlogs Turn off the gas valve and allow the unit to cool before opening door to carefully remove the logs The pilot light generates enough heat to burn someone If...

Страница 44: ...t off electrical supply 3 Lift off cast top and place on a soft surface 4 Loosen bolts securing cast front slide light as sembly bracket upward to release 5 Remove two 2 screw to remove bulb housing L...

Страница 45: ...7 Remove the cast front See page 13 for instruc tions 8 Remove the glass front assembly by opening the the 2 latches 9 Carefullyremovethelogs embersandrockwool 10 Remove burner see diagram below Note...

Страница 46: ...743 201 Cast Top Charcoal Grey 743 205 Cast Top Timberline Brown 743 207 Cast Top Seaside Sand 15 743 211 Cast Left Charcoal Grey 743 215 Cast Left Timberline Brown 743 217 Cast Left Seaside Sand 16...

Страница 47: ...rifice LP 911 039 Novasit Pilot Hood 2 way 911 137 Pilot Hood Clip 911 037 Flame Sensor 911 038 Flame Electrode 904 240 Burner Orifice 37 NG 904 390 Burner Orifice 52 LP 904 529 5 32 Allen Key Pilot O...

Страница 48: ...48 Hampton H35 10 Direct Vent Freestanding Gas Stove 48 notes...

Страница 49: ...Hampton H35 10 Direct Vent Freestanding Gas Stove 49 49 notes...

Страница 50: ...50 Hampton H35 10 Direct Vent Freestanding Gas Stove 50 notes...

Страница 51: ...d if requested It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufactur...

Страница 52: ...staller ____________________________________________________________ Phone ____________________________________________________________ Date Installed _________________________________________________...

Отзывы: