38
PART 4. VENTING
E. CONDENSATE REQUIREMENTS
This is a condensing high efficiency appliance, therefore this unit has
a condensate removal system. Condensate is nothing more than water
vapor derived from the combustion products, similar to an automobile
when it is initially started. This condensate does have a low pH and
should be treated with a Condensate Neutralizer Filter. This filter contains
either lime or marble rocks, which will neutralize the condensate. The
outlet of the filter is sized for 3/4" hose.
It is very important that the
condensate line is sloped away from and down to a suitable inside
drain.
A condensate neutralizer and a condensate pump kit are available
from the Manufacturer. It is also very important that the condensate
line is not exposed to freezing temperatures, or any other type of
blockage. Plastic tubing or PVC pipe should be the only materials used
for the condensate line. Steel, brass, copper or others will be subject
to corrosion and deterioration. A second vent may be necessary to
prevent condensate line vacuum lock if a long horizontal run is used. The
appliance has an automatic safety device that will shut it down in the
event of a condensate drain blockage. Please test annually.
Maximum volume of condensate produced is 11 gallons per hour per
1,000,000 BTU of gas burned.
In a common vent system, DO NOT POWER
THE UNIT OFF! Equipment damage may
occur. To disable operation, turn off gas,
NOT power. If you have any questions,
please call Technical Support.
WARNING
Содержание XL800
Страница 6: ...6 PART 1 GENERAL INFORMATION As a Stand Alone Appliance HOT CONTROL MENU NAVIGATION ...
Страница 7: ...7 PART 1 GENERAL INFORMATION Appliance as Part of a Cascade HOT CONTROL MENU NAVIGATION ...
Страница 19: ...19 PART 2 ELECTRICAL B INTERNAL WIRING CONNECTION continued XL BCB LAYOUT ...
Страница 21: ...21 PART 2 ELECTRICAL XL CASCADE BOX ...
Страница 31: ...31 PART 4 VENTING Direct Vent Terminal Clearances ...
Страница 32: ...32 PART 4 VENTING Direct Vent Terminal Clearances continued Other Than Direct Vent Terminal Clearances ...
Страница 33: ...33 PART 4 VENTING Other Than Direct Vent Terminal Clearances continued ...
Страница 69: ...69 PART 10 PARTS BREAKDOWN 1A 1B PART 10 PARTS BREAKDOWN 2 ...
Страница 70: ...70 PART 10 PARTS BREAKDOWN 3 4 5 6 7 8 9A 9B 9C 10 4 ...