15
F. DIMENSIONS
PART 1. GENERAL INFORMATION
(TABLE 1-2) HX DATA
*At 97% thermal efficiency with 86
o
F incoming water to heat exchanger
**At 95% thermal efficiency with 140
o
F incoming water to heat exchanger
† Individual appliance piping pressure drop used in the tables is based on 20
feet of straight pipe, 6 elbows, 2 tees, 2 full port ball valves and 2 unions
(TABLE 1-1) APPLIANCE DIMENSIONS
240 Volt Power Supply
Model
Amps/unit
Boiler Pump
Total amps
Boiler
HWH 800
3.85
0.40
4.25
HWH 1000
5.1
0.48
5.58
HWH 1500
7.95
0.83
8.78
208 Volt Power Supply
Model
Amps/unit
Boiler Pump
Total amps
Boiler
HWH 800
4.44
0.47
4.91
HWH 1000
5.88
0.55
6.44
HWH 1500
9.17
0.96
10.13
ELECTRICAL CHARACTERISTICS FOR PRODUCTS
Note: No load switching is possible directly from the BCB or CCB, it may only switch a relay signal.
Model
Amps/unit
Heater Pump
Total amps
Boiler
HWD 800
3.85
0.83
4.68
HWD 1000
5.1
1.15
6.25
HWD 1500
7.95
1.77
9.72
Model
Amps/unit
Heater Pump
Total amps
Boiler
HWD 800
4.44
0.96
5.40
HWD 1000
5.88
1.32
7.21
HWD 1500
9.17
2.04
11.22
Exhaust
Outlet
Gas Inlet
Height
Water Inlet
Width
B
B
C
A
Water Outlet
A
Air Intake
Length
Heater/Boiler
Model
Width
Height
Depth
A (VIC Groove)
B
C
ShippingWeight
in
mm
in
mm
in
mm
in
mm
in
mm
in
mm
lb
kg
XL800
31.6
803.2
51
1295
51
1295
2
50
6
152
1
25
650
295
XL1000
31.6
803.2
51
1295
69.2
1757.4
2
50
6
152
1
25
750
340
XL1500
31.6
803.2
51
1295
69.2
1757.4
2
50
8
203
1.5
38
850
385
Model
Input
Water Heater*
Output
Boiler Output**
Recovery @
100˚F∆T
(55.6˚C∆T)
Recovery @
80˚F∆T
(44.5˚C∆T)
Recovery @
60˚F∆T
(33.3˚C∆T)
Water Flow Rate &
Pressure Drop
DHW †
Water Flow Rate &
Pressure Drop
Heating
BTU/Hr
kW
BTU/Hr
kW
BTU/Hr
kW
GPH
LPH
GPH
LPH
GPH
LPH
GPM@FT
LPM@M
GPM@FT
LPM@M
XL800
795,000
233
up to
771,150
up to
226
up to
755,250
up to
221
926
3,505
1,157 4,380 1,543
5,841
51.4@12'
30.2@7'
XL1000
999,999
293
up to
969,999
up to
284
up to
949,999
up to
278 1,164 4,406 1,456 5,512
1,941
7,348
[email protected]' [email protected] [email protected]' [email protected]
XL1500 1,475,000 432
up to
1,430,750
up to
419
up to
1,401,250
up to
410
1,718 6,494 2,147
8,115
2,863 10,822 [email protected]' [email protected] [email protected]' [email protected]
Содержание XL800
Страница 6: ...6 PART 1 GENERAL INFORMATION As a Stand Alone Appliance HOT CONTROL MENU NAVIGATION ...
Страница 7: ...7 PART 1 GENERAL INFORMATION Appliance as Part of a Cascade HOT CONTROL MENU NAVIGATION ...
Страница 19: ...19 PART 2 ELECTRICAL B INTERNAL WIRING CONNECTION continued XL BCB LAYOUT ...
Страница 21: ...21 PART 2 ELECTRICAL XL CASCADE BOX ...
Страница 31: ...31 PART 4 VENTING Direct Vent Terminal Clearances ...
Страница 32: ...32 PART 4 VENTING Direct Vent Terminal Clearances continued Other Than Direct Vent Terminal Clearances ...
Страница 33: ...33 PART 4 VENTING Other Than Direct Vent Terminal Clearances continued ...
Страница 69: ...69 PART 10 PARTS BREAKDOWN 1A 1B PART 10 PARTS BREAKDOWN 2 ...
Страница 70: ...70 PART 10 PARTS BREAKDOWN 3 4 5 6 7 8 9A 9B 9C 10 4 ...