PART 3. GAS CONNECTION
HW 800
Fan Type
Maximum RPM
Minimum RPM
Ametek 8.9 High Output En
8300
2739
HW 1000
Fan Type
Maximum RPM
Minimum RPM
Ametek 8.9 High Output En
8800
2728
HW 1500
Fan Type
Maximum RPM
Minimum RPM
Ametek 8.9 High Output En
10400
2496
(TABLE 3-5) FAN SPEED REQUIREMENTS
F. SETTING THE MINIMUM LOAD
Set the minimum load once the
maximum load has been set, set the
fan speed in the service function to
the minimum RPM setting. In order
to set or adjust the minimum load,
turn the screw [2] for the minimum
setting. Turn the screw according
to the markings on the gas valve,
to increase or decrease the CO2
percentage.
• If the measuring process takes
more than 40 minutes, the
appliance will return to the
automatic mode. If so required,
enter the Service function
another time.
• When you are done setting the
valve, press stop in the Service
function to return to normal run
mode.
Содержание XL800
Страница 6: ...6 PART 1 GENERAL INFORMATION As a Stand Alone Appliance HOT CONTROL MENU NAVIGATION ...
Страница 7: ...7 PART 1 GENERAL INFORMATION Appliance as Part of a Cascade HOT CONTROL MENU NAVIGATION ...
Страница 19: ...19 PART 2 ELECTRICAL B INTERNAL WIRING CONNECTION continued XL BCB LAYOUT ...
Страница 21: ...21 PART 2 ELECTRICAL XL CASCADE BOX ...
Страница 31: ...31 PART 4 VENTING Direct Vent Terminal Clearances ...
Страница 32: ...32 PART 4 VENTING Direct Vent Terminal Clearances continued Other Than Direct Vent Terminal Clearances ...
Страница 33: ...33 PART 4 VENTING Other Than Direct Vent Terminal Clearances continued ...
Страница 69: ...69 PART 10 PARTS BREAKDOWN 1A 1B PART 10 PARTS BREAKDOWN 2 ...
Страница 70: ...70 PART 10 PARTS BREAKDOWN 3 4 5 6 7 8 9A 9B 9C 10 4 ...